Operation
11 Operation
11.1 Safety information
Danger
Risk of ignition of a potentially explosive gas/air atmosphere!
When commissioning the EX fan, the fundamental information from DGUV 113-001 (explosion protection
rules (EX-RL)) and TRGS 727 (avoidance of risk of ignition as a result of electrostatic charges) must be
known.
Do not open or tip the fan if an explosive atmosphere exists.
Warning: Hazard from electrical voltage or moving components.
The fan may only be operated by adequately qualified persons, details see Table 1 Qualifications, page 3.
Important
Damage to the fan because of condensation water.
Ensure regular switch-on time of 2 hours per week
Only use the fan in accordance with the operating
instructions and the operating instructions for the
motor.
The EX fans have been admitted for S1 continuous
operation.
12 Troubleshooting/maintenance/repair
Safety information
Observe 3 Important safety information, page 2
Danger
Loss of explosion protection
The manufacturer must always be consulted before any maintenance or repair work is carried out!
Repairs should preferably always be carried out by the manufacturer! Exceptions can be made for non-
relevant components such as terminal boxes, screwed cable connections, etc. These can also be dealt
with on-site by the operator's qualified staff (authorised personnel). Non-compliance will result in the
ATEX certification being revoked!
For ATEX-certified products, the repair or replacement of fan components is expressly only permitted
after consultation with the manufacturer and only if the manufacturer's original parts are used!
After repair, the fan/system must be subjected to an inspection in accordance with local conditions,
regulations and laws (in Germany: §14 Abs 6 der BetrSichV Industrial Safety Regulation). This does not
apply to repairs carried out by the manufacturer.
| 006