Axial fans/Jet fans AXC, AXCBF, AXR, AXS, AJR, AJ8 Installation and Operating Instructions Document in original language | · 008 GB
© Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Contents 1 2 3 4 5 6 7 General information .........................................1 1.1 Warning symbols ...................................1 1.1.1 Instruction symbols.....................1 Important safety information .............................1 2.1 Personnel .............................................2 2.2 Personal protective equipment..................2 2.3 5 rules of electrical safety ........................2 Warranty .......................................................
General information | 1 General information 1.1 Warning symbols Danger Caution Direct hazard Failure to comply with this warning will lead directly to death or to serious injury. Hazard with a low risk Failure to comply with this warning may lead to moderate injuries. Warning Important Potential hazard Failure to comply with this warning may lead to death or serious injury. Hazard with risk of damage to objects Failure to comply with this warning will lead to damage to objects.
2 | Warranty 2.1 Personnel The fan may only be used by qualified, instructed and trained personnel. The persons must know the relevant safety directives in order to recognise and to avoid risks. The individual activities and qualifications can be found in Table 1 Qualifications, page 2.
Delivery, transport, storage | 4.1 Delivery Each fan leaves our plant in an electrically and mechanically proper condition. We recommend transporting the fan to the installation site in the original packaging. Checking delivery ♦ Check the packaging and the fan for transport damage. Any findings should be noted on the cargo manifest. ♦ Check completeness of the delivery. Unpacking Warning When opening the transport packaging, there is a risk of damage from sharp edges, nails, staples, splinters etc.
4 | Description 5 Description 5.1 General • The fan conveys air in an axial direction from the intake side via the electric motor to the outlet side. (except AXCBF). • The electrical connection is made through a terminal box installed on the outside of the housing (except AXCBF). Sensors (optional) Sensors can be connected to the fan to monitor the roller bearings and for vibration monitoring. Standstill heating (optional) The standstill heating starts when the motor switches off and vice versa. 5.1.
Description | 5.1.
6 | Description 5.2.1 Construction 6 3 1 4 2 7 5 1 Motor 3 Terminal box 5 Mounting feet 2 Impeller 4 Housing 6 Motor brackets 7 Guide vane 5.2.2 only available for -PV version Types & variants Table 3 Axial fan base types Type Description AXC Standard fan of the AXC-series. As a default, the fans are provided in protection class IP55, ISO F. AXS Special fans for marine, oil and gas applications.
Description | 5.2.
8 | Description 5.3 Description Jet fans 5.3.1 Description AJR/AJ8 • In B3 conventional motors, the motor bracket is made from galvanized steel sheet. B30 “pad mounted” motors are fitted in the housing via threaded rods or a welded motor support. • The fan conveys air in an axial direction from the intake side via the electric motor to the outlet side. • The silencers are equipped with protection grille made of galvanized steel.
Description | Table 6 Dimensions AJ8, AJR F E L 211 H AJR F B F B E L 211 H AJ8 Size H [mm] B [mm] E [mm] F [mm] L [mm] AJ8 315 (B), (F) 365 375 325 678 1535 AJ8 355 (B), (F) 395 400 355 678 1695 AJ8 400 (B), (F) 445 500 460 727 1875 ARJ 315 (B), (F) 365 223 265 433 1535 ARJ 355 (B), (F) 465 243 305 473 1695 ARJ 400 (B), (F) 505 266 350 516 1875 5.4 Description AXCBF Directly powered axial fan with motor outside the air flow.
10 | Description 5.4.1 Construction 1 Motor 2 Impeller 3 Housing 4 Motor bracket 1 4 2 3 Table 7 Dimensions Size 250 — 500 Size 630 — 800 ½I H A A H F ½I I C D C D I F B Size [mm] A ØB ØC ØD ØF ØH I AXCBF 250 535 448 328 250 280 10 4x90° AXCBF 315 535 452 385 320 355 10 8x45° AXCBF 400 625 585 480 401 450 10 8x45° AXCBF 500 660 695 590 12 12x30° 790 728 634 504 - 560 AXCBF 630 690 12 12x30° AXCBF 800 880 890 797 - 860 12 16x22.
Description | 5.5 Intended use All axial fans • The temperature of the air transported through the fan must not exceed the temperature range stated on the name plate. • For the temperature resistance of the smoke extraction fans (K), (B), (F), which can also be used to extract CO, please refer to the name plate (e.g. 300°C/120 min).
12 | Name plate and type key 6 Name plate and type key 3 EN 12101-3 (2015) Powered Smoke and Heat Control ventilator Type: AXC 355-6/10°-2(B)-P Stage 1 of 2 Order no. / Production no.: 0003500662 / 1251364 Manufacturing date: 06/2021 Made in: Germany Voltage: 400V Y Frequency: 50 Hz Nominal power at shaft (P2): Nominal current: 0,75 kW IE3 1,66 A Cos φ: 0,79 Insulation class: H Protection class, motor: IP55 Fan impeller speed: 2865 1/min Weight: 38 kg Max.
Installation | 7 Installation Safety information Danger: Risk that the fan does not work in case of fire. ♦ Use installation material with fire resistance classes that meet temperature requirements. Warning: Danger from falling fan or fan parts. ♦ Check the surface before installation for load bearing capacity. ♦ Consider all static and dynamic loads when selecting hoisting equipment and fastening components.
14 | Installation Mounting feet Depending on the kind of fan and the construction size, mounting feet are either included in the delivery or available as accessories. If you are not sure, check the online catalogue or contact Systemair. Avoid resonance frequencies Important Risk of damage to the fan due to resonance frequencies ♦ The minimum fan speed should be double the resonance frequency of the anti-vibration system (vibration dampers). ♦ To avoid resonance frequencies, see 8.
Installation | Lifting and positioning The weight of the fan units varies depending on the motor size and accessories. As a result, the fan unit can also be very bulky and heavy. You can find precise information on the name plate or the data sheet. Caution Risk of parts falling down ♦ When fitting the fan, pay attention to its weight and the weight of the components. Lifting Positioning ♦ Lift the fan unit slowly and carefully. ♦ Observe the arrows on the name plate or the housing of the fan.
16 | Installation 7.2.1 Installation of the ventilation system Preconditions ♦ The air flow of the fan must be able to open the air operated damper (LRK). Installation duct 1 ♦ Do not place a duct bend directly before or after the fan! • This can cause damage to the bearings or other parts of the fan. • The duty point may not be reachable. min. 2,5xD • The fan may make noise. ♦ Ensure a direct, smooth and constant air flow to the device. Ensure a free exhaust, see the following pictures.
Installation | 7.2.2 Installation of flexible connections Important Increasing noise emission ♦ Do not install the flexible connections at an angle. Note: When fitting the flexible connections, make sure that they are fitted according to the installation length (Table 9 Flexible connections — Installation length, page 17), without compression or tensile strain. They must not be used to compensate any lack of precision in the assembly. Table 9 Flexible connections — Installation length EV (-25...
18 | Installation 7.2.3 Installation silencer ♦ Ensure correct installation of the silencer. • This can cause damage to the bearings or other parts of the fan. • The duty point may not be reachable. • The fan may make noise. ♦ Ensure a direct, smooth and constant air flow to the device. Ensure a free exhaust, see the following pictures. ♦ To reduce transmission of vibration to the duct system, we recommend flexible connections from our accessory range, see 5.2.3 Accessories, page 7.
Electrical connection | 7.3.1 Deflector For optimal guidance of the air current, a deflector made of galvanized steel sheet can be mounted on the pressureside silencer (accessory). The deflector as accessory for AJR/AJ8 is delivered in a separate package. ♦ Before installing the jet fan, fasten the deflector on the silencer of the pressure side (see arrow). ♦ Position the deflector fins so that after fastening the jet fan to the ceiling, the air flow is directed downwards at a 10° angle.
20 | Electrical connection Table 10 Motor protection Type Motor protection Thermal protection, standard Speed regulation Fans for long-term operation —20 ° C...55 °C only, see 5.1.2 Temperature types, page 4 By customer PTC Possible via frequency converter AXC (B),(F),(K) AXR (B),(F),(K) AXC (B)-P, (F)-P AXC (B)-PV, (F)-PV AJ8 (B), (K), (F) AJR (B), (K), (F) By customer- must be bypassed in case of fire without (PTC optional) Possible via frequency converter 8.
Electrical connection | 8.2.2 Wiring diagram Important Wrong connection can damage or destroy the motor. ♦ Use the information on the nameplate to select the correct connection diagram.
22 | Commissioning 9 Commissioning Warranty claims can only be made if commissioning work is carried out correctly and written evidence thereof is provided. It is recommended to fill out the commissioning report chapter 15. Safety information ♦ Commissioning may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 2. Preconditions ♦ Installation and electrical connection have been correctly performed. ♦ Ground cable is connected. ♦ Cable glands are tight.
Troubleshooting/maintenance/repair | 11 Troubleshooting/maintenance/repair Safety information ♦ Troubleshooting/maintenance/repair may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 2. ♦ Observe the 5 rules of electrical safety, see 2.3 5 rules of electrical safety, page 2. ♦ The impeller must be at a standstill. 11.
24 | Troubleshooting/maintenance/repair Note: For all other damage/defects, please contact Systemair. Defective safety-relevant fans (for Ex and smoke extraction applications) must be replaced completely. 11.2 Maintenance Warranty claims can only be made if maintenance work is carried out correctly and written evidence thereof is provided. We recommend regular maintenance intervals to ensure continuous fan operation. These maintenance intervals are specified in the “Activities” table below.
Troubleshooting/maintenance/repair | Activities for fans used for emergency operation. cont'd Operational readiness of the emergency system Allow the "emergency" system to run for 15 minutes X Function of the “emergency” control Test whether the “emergency” control effectively bridges all the other controls and switches X Function of the standstill heating Switch the motor off. The standstill heating must switch on automatically and remain switched on X 11.
26 | Cleaning 11.5 Spare parts ♦ Use original spare parts from Systemair only. ♦ When ordering spare parts, please specify the serial number of the fan. This can be found on the name plate. 12 Cleaning Safety information ♦ Cleaning may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 2. ♦ Observe the 5 rules of electrical safety, see 2.3 5 rules of electrical safety, page 2! Preconditions ♦ The power supply has been switched off (all-pole circuit breaker).
Commissioning Report | 15 Commissioning Report Warranty claims can only be made if commissioning work is carried out correctly and written evidence thereof is provided. Fan Description: Article no.: Manufacturing order no.: Installer Company: Contact person: Company address: Tel. no.: Email: Operator (Place of installation) Company: Contact person: Company address: Tel. no.
28 | Commissioning Report Measured data at commissioning Voltage [V]: Temp.
| 008
Tel.: +49 (0)7930/9272-0 Fax: +49 (0)7930/9273-92 info@systemair.de www.systemair.de Axial fans/Jet fans · Installation and Operating Instructions · · en_GB · 2021-06-16 · 008 Systemair GmbH Seehöfer Str.