Chiller AQVC 85-140 Air Cooled Condensing Units Engineering Data Manual 92 to 151 kW
| AQVC Outstanding Strength Points Units with R410A refrigerant (it will be the real replacement of R22). As near azeotropic mixture it behaves like a homogeneous substance (reduced service problems in case of leakage or re-charge) with negligible temperature glide. Refrigerant with superior thermo-dynamical proprieties compared to R22 and R407C, it allows to have more efficiency or compact and lighter systems and larger operating limits.
AQVC | Specifications (continued) Electrical board The electrical board is located in a metal case arranged outside the unit and protected by a vertically pivoted access door. The metal case has an IP54 protection rating and is complete with grilles for natural air ventilation. Standard equipment 3 Back light display. 3 Digital pressure and temperature reading kit. Electronic control 3 High ambient pressure control.
| AQVC Refrigerant Flow Diagram - AQVC Units S A M AT 1 OIL EQUAL. B 3 G S BT S 3 2 D 3 COMPONENTS 1 Compressor tandem Scroll Type 2 Air cooled condenser 3 Globe valve SAFETY/CONTROL DEVICES A High pressure switch (40.5 bar) AT High pressure transducer B Low pressure switch (1.
AQVC | Operating Limits 85 AQVC Evaporating temperature Ambient Air Min. 95 Max. Min. 105 Max. °C Air entering temperature External static pressure Min. 115 Max. Min. Max. 125 Min. Max. 140 Min. Max.
| AQVC Technical Data - AQVC 85 to 140 - R410A - STD/HSE/HPF - BLN Version AQVC Sizes - STD/HSE/HPF - BLN Version 85 95 105 115 125 140 Cooling Capacity * kW 92.1 103.2 113.2 121.8 134.7 151.0 Input Power (Compressor) kW 25.3 29.3 32.0 34.9 38.3 43.
AQVC | Technical Data - AQVC 85 to 140 - R410A - STD/HSE/HPF - ELN Version AQVC Sizes - STD/HSE/HPF - ELN Version 85 95 105 115 125 140 Cooling Capacity * kW 89.0 99.4 108.7 116.6 131.6 147.2 Input Power (Compressor) kW 26.8 31.3 34.3 37.5 39.8 45.
| AQVC Technical Data - AQVC 85 to 140 - R410A - HT AQVC Sizes - HT 85 95 105 115 125 140 Cooling Capacity * kW 95.0 106.8 117.7 127.0 137.2 153.8 Input Power (Compressor) kW 23.9 27.4 29.8 32.3 37.1 42.
AQVC | Electrical Data - AQVC 85 to 140 - R410A - STD Units Compressor data - 400 V/3Ph/50Hz NOMINAL Circuit 1 AQVC 85 Circuit 2 Circuit 1 AQVC 95 Circuit 2 Circuit 1 AQVC 105 Circuit 2 Circuit 1 AQVC 115 Circuit 2 Circuit 1 AQVC 125 Circuit 2 Circuit 1 AQVC 140 Circuit 2 MAX Istartup LRA (A) Power factor coefficient (NOM) 16 95 0.8 9.1 16 95 0.8 9.1 16 95 0.8 11.3 9.1 16 95 0.8 7.1 12.7 10.2 21 111 0.8 COMP 2 7.1 12.7 10.2 21 111 0.8 COMP 1 7.1 12.7 10.
| AQVC Electrical Data - AQVC 85 to 140 - R410A - STD Units (cont.) Units - 400 V/3Ph/50Hz - BLN Version Sizes AQVC 85 AQVC 95 AQVC 105 AQVC 115 AQVC 125 AQVC 140 27.4 30.6 33.1 35.5 41.4 45.9 38.8 43.2 46.7 50.2 57.3 62.9 Nominal 49.8 55.3 60.4 65.5 76.5 84.2 Maximum 68.5 88.5 90.5 92.5 113.8 131.8 147.5 178.5 186.5 188.
AQVC | Electrical Data - AQVC 85 to 140 - R410A - HSE/HPF/HT Units Compressor data - 400 V/3Ph/50Hz NOMINAL Circuit 1 AQVC 85 Circuit 2 Circuit 1 AQVC 95 Circuit 2 Circuit 1 AQVC 105 Circuit 2 Circuit 1 AQVC 115 Circuit 2 Circuit 1 AQVC 125 Circuit 2 Circuit 1 AQVC 140 Circuit 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 COMP 1 COMP 2 MAX Pnom (kW) Inom (A) Pmax (kW) Imax FLA (A
| AQVC HPF Version Fan Performance Data AQVL/AQVH Sizes 85 95 105 115 125 140 Fan Static Pressure (Pa) Fan RPM Parameter in Service Level Max Speed (Vdc) Sound Power Level dB(A) 40 880 8.2 88 60 920 8.5 89 80 950 8.7 90 100 990 9.0 91 120 1030 9.3 92 40 880 8.2 88 60 920 8.5 89 80 950 8.7 90 100 990 9.0 91 120 1030 9.3 92 40 870 8.1 88 60 910 8.4 89 80 950 8.7 90 100 990 9.0 91 120 1030 9.3 92 40 870 8.1 88 60 910 8.
AQVC | Sound Data STD/HSE BLN Versions Octave Band (Hz) 63 125 250 500 1000 2000 4000 8000 Sound Power Level dB(A) Sound Pressure Level* dB(A) 85 98 91 86 82 81 74 69 69 85 53 95 98 91 86 82 81 74 69 69 85 53 105 98 91 86 82 81 74 69 69 85 53 115 98 91 86 82 81 74 69 69 85 53 125 102 95 89 86 84 78 72 72 89 57 140 102 95 89 86 84 78 72 72 89 57 Sizes STD/HSE ELN Versions Octave Band (Hz) 63 125 250 500 1000 2000 4000 8000
| AQVC Performance Data - AQVC 85 to 140 - R410A - STD/HSE/HPF - BLN Version AQVC 25 Temp. Sizes evap. P P BLN (°C) cool abs* Version (kW) (kW) AQVC 85 AQVC 95 AQVC 105 AQVC 115 AQVC 125 AQVC 140 Outdoor air temperature (°C) 30 32 35 38 40 42 45 48 P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) 65.0 31.0 72.8 35.9 79.9 39.
AQVC | Performance Data - AQVC 85 to 140 - R410A - STD/HSE - ELN Version AQVC Temp. Sizes evap. ELN (°C) Version AQVC 85 AQVC 95 AQVC 105 AQVC 115 AQVC 125 AQVC 140 Outdoor air temperature (°C) 25 30 32 35 38 40 42 45 P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) P cool (kW) P abs* (kW) 1 84.5 20.9 80.5 23.1 79.0 24.1 76.5 25.6 73.6 27.1 71.
| AQVC Performance Data - AQVC 85 to 140 - R410A - HT Outdoor air temperature (°C) AQVC 25 30 32 35 38 40 42 45 48 50 Temp. Sizes evap. P P P P P P P P P P P P P P P P P P P P HT (°C) cool abs* cool abs* cool abs* cool abs* cool abs* cool abs* cool abs* cool abs* cool abs* cool abs* Version (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) AQVC 85 AQVC 95 AQVC 105 AQVC 115 AQVC 125 AQVC 140 1 90.1 18.7 85.9 20.7 84.2 21.5 81.6 22.8 78.5 24.2 76.
AQVC | Dimensions (mm) - AQVC - R410A - Sizes 85 to 115 30 Bottom view P3 P2 P4 4xØ17 E-F 382 1382 492 30 1040 P1 Front view 40 Side view M 2185 1955 L R S 4 xØ50 G 247 802 P Q I H 304 76 53 76 76 1066 1100 1250 (Only for shipment) 2555 988 P4 70 P1 262 P3 1612 382 56 988 988 1100 P2 56 Top view 70 2256 E F G H I Electrical auxiliary lines Electrical power supply High pressure tap Low pressure tap Gauge kit (accessory) 53 L M P Q Main switch Control keypa
| AQVC Dimensions (mm) - AQVC - R410A - Sizes 125 & 140 30 Bottom view P3 P2 P4 4xØ17 382 E-F 1982 492 30 1040 P1 Side view Front view M L I Q R S 247 G 76 76 304 4xØ50 P 802 H 53 76 988 988 P4 70 988 1100 70 Top view 56 3155 P2 P1 262 E F G H I P3 2212 2856 Electrical auxiliary lines Electrical power supply High pressure tap Low pressure tap Gauge kit (accessory) L M P Q Main switch Control keypad / display Discharge circuit 2 Suction circuit 2 53 1250(Only for
AQVC | Unit Clearances (in mm) Installation of single units Installation of several units A1 WALL A A2 1.5 m WALL A A1 A2 A3 1.5 m WALL D 2.0 m WALL B WALL D WALL B 1.0 m 1.
Tel. +39 0362 680 1 Fax +39 0362 680 693 info@systemair.it www.systemair.com Systemair · February 2012 · EDM AQVC-S.1GB/02.12 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.