EDM SyScroll 40 75 Air

|
SyScroll 40-75 Air
22
Model 40 45 50 60 65 75
Nominal cooling capacity (1) kW 40,8 44,8 51,9 60,9 68,9 76,7
Power input (1) kW 14,0 16,2 18,6 20,5 23,5 27,9
EER (1) kW/kW 2,91 2,77 2,79 2,97 2,93 2,75
Energy Efciency Class B C C B B C
ESEER (1) kW/kW 4,08 3,87 3,89 4,01 4,07 3,73
Number of refrigerant circuits 1
Total capacity steps % 50-100 50-100 50-100 44-56-100 50-100 50-100
Compressor
Number 2
Type / Oil type Scroll / POE
Internal heat exchanger
Number 1
Type Plate
Water ow rate l/h 6.884 7.572 8.774 10.317 11.680 13.032
Water pressure drop kPa Refer to pressure drop curves
Antifreeze heater W 35
External heat exchanger
Number 1
Type Finned Tubes Coils
Total face area m
2
2,59 2,59 2,59 3,18 3,18 3,18
Fans
Number 1
Nominal speed rpm 680 680 680 900 900 900
Air ow rate m
3
/h 14.000 14.000 13.200 21.100 21.100 21.100
Input power kW 0,98 0,98 0,98 2,00 2,00 2,00
Input power (*) kW 2,67 2,67 2,67 2,67 2,67 2,67
External static pressure (*) Pa 0 to 120
Water connections (Internal heat exchanger)
Type Male Gas Threaded
Inlet diameter / Outlet diameter inch 2”
Water connections (Desuperheater)
Type Male Gas Threaded
Inlet diameter / Outlet diameter inch 1”
Weight
Shipping kg Refer to weight table
Operating kg Refer to weight table
Dimensions
Length mm 1.750 1.750 1.750 2.200 2.200 2.200
Width mm 1.100 1.100 1.100 1.100 1.100 1.100
Height mm 1.580 1.580 1.580 1.580 1.580 1.580
Acoustic data
Sound power level (2) dB(A) 80 81 81 85 86 86
Sound pressure level (3) dB(A) 49 49 49 54 54 54
(1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
(2) Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.
(3) Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
(*) HPF / HT Versions with EC fan motor.
Technical data - SyScroll 40-75 Air CO_ - (STD-HPF-HT)
Standard and High Pressure Fan Versions