EDM SyScroll 40 75 Air
|
SyScroll 40-75 Air
26
SyScroll Air RE_ - (STD/HPF/HT) 40 45 50 60 65 75
Nominal cooling capacity (1) kW 43,2 48,8 56,9 67,4 73,8 84,5
Power input (1) kW 13,9 16,3 18,8 20,7 23,6 28,3
Number of refrigerant circuits 1
Total capacity steps % 50-100 50-100 50-100 44-56-100 50-100 50-100
Fans
Number 2
Nominal speed rpm 680 680 680 900 900 900
Air ow rate m
3
/h 14.000 14.000 13.200 21.100 21.100 21.100
Input power kW 0,98 0,98 0,98 2,00 2,00 2,00
Input power (*) kW 2,67 2,67 2,67 2,67 2,67 2,67
External static pressure (*) Pa 0 to 120
Acoustic data
Sound power level (2) dB(A) 80 81 81 85 86 86
Sound pressure level (3) dB(A) 49 49 49 54 54 54
SyScroll Air RE_S 40 45 50 60 65 75
Nominal cooling capacity (1) kW 41,6 46,7 54,0 64,9 70,7 80,6
Power input (1) kW 14,2 16,9 19,7 21,0 24,0 29,4
Number of refrigerant circuits 1
Total capacity steps % 50-100 50-100 50-100 44-56-100 50-100 50-100
Fans
Number 1
Nominal speed rpm 530 530 530 720 720 720
Air ow rate m
3
/h 11.000 11.000 10.300 16.000 16.000 16.000
Input power kW 0,57 0,57 0,57 1,27 1,27 1,27
Acoustic data
Sound power level (3) dB(A) 74 75 75 78 79 79
Sound pressure level (4) dB(A) 42 44 44 46 47 47
Compressor
Number 2
Type / Oil type Scroll / POE
External heat exchanger
Number 1
Type Finned Tubes Coils
Total face area m
2
2,59 2,59 2,59 3,18 3,18 3,18
Refrigerant connections
Type To be brazed
Inlet diameter / Outlet diameter inch 5/8” / 1”3/8 7/8” / 1”3/8
Weight
Shipping kg Refer to weight table
Operating kg Refer to weight table
Dimensions
Lenght mm 1.750 1.750 1.750 2.200 2.200 2.200
Width mm 1.100 1.100 1.100 1.100 1.100 1.100
Hight mm 1.580 1.580 1.580 1.580 1.580 1.580
(1) Data refers to 7°C evaporating temperature and 35°C condenser inlet air temperature.
(2) Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.
(3) Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.
(*) HPF / HT Versions with EC fan motor.
Technical data - SyScroll Air RE
Remote Evaporator Version