EDM SyScroll 40 75 Air
SyScroll 40-75 Air
|
5
Air cooled condenser coil
Outdoor heat exchangers are nned tubes coils. Coils
are built with internally grooved copper tubes expanded
into corrugated aluminium ns. Fin pitch is differentiated
between the two coil conguration (condensing only, re-
versible) in order to optimize operating conditions.
Condenser fans
Each unit has one axial fan, xed speed type, 800 mm
diameter. According to the version, the fan is cabled in
order to have high speed (700 to 900 rpm) for BLN ver-
sion and low speed (530 to 680 rpm) to reduce the sound
level for SLN version. The fan motor has IP54 grade and is
equipped with a thermal overload protection.
A pressure actuated fan speed controller can be supplied
as eld-installed accessory or factory-mounted option. It
allows the unit operating in cooling mode at ambient tem-
perature down to -18 °C.
On HT / HPF versions, a brushless fan motor is controlled
by a 0-10 V signal regulating the speed from 0 to 1110
rpm. This special fan allows the unit to be used in two
applications:
High ambient temperature: The fan provides high air
ow at maximum speed in order to keep a low con-
densing temperature while operating at high air tem-
perature.
Ducted installation: The fan provides high static pres-
sure in order to allow the unit to be ducted.
All types of fans are tted with a protective grille on top.
Refrigerant circuit
Refrigerant circuit is equipped with hermetic scroll com-
pressors tandem, sight glass, lter-drier and mechanical
expansion valve (electronic expansion valve is available
as an option).
Heat pump units refrigerant circuit is also provided with
4-way reversing valve, bi-ow lter drier, bi-ow expan-
sion valve, liquid separator and liquid receiver.
Hydraulic circuit
Thanks to the design exibility on the hydraulic circuit, all
the units can be congured in several ways:
BASIC unit: Unit is without pump and tank. The hydrau-
lic circuit includes the following components: water l-
ter, ow switch, 3/8” in/out water valves, water safety
valve, automatic air vent, hydrometer and Victaulic con-
nections (allowing quick connections in order to update
the circuit with buffer tank and pumps). All water piping
is covered with 19 mm thick insulation.
1P: 1-Pump unit having same equipment as BASIC one
+ a pump with available static pressure of 150 kPa. Two
air vents are supplied for this conguration.
1PT: 1-Pump + Tank unit having same equipment as 1P
one + a buffer tank to be installed inside the unit. The
tank is covered with 10 mm thick polyethylene insula-
tion and is equipped with a 200 W antifreeze heater.
2P: 2-Pump unit having same equipment as BASIC one
+ 2 pumps with available static pressure of 150 kPa.
Each pump can be isolated and replaced with the help
of two Victaulic valves. A non-return valve is provided
to protect each pump from pumping water in the dis-
charge pipe of the other pump. Two air vents are also
supplied for this conguration.
2PT: 2-Pump + Tank unit having same equipment as 2P
one + a buffer tank to be installed inside the unit. The
tank is covered with 10 mm thick polyethylene insulation
and is equipped with a 200 W antifreeze heater. In pump
equipped unit, the head of the pump is insulated with a
19 mm thick insulation to avoid condensation on it.
Water connections are 2” male gas threaded type.
Control panel
A new optimized control is supplied on all the units with a
simple user interface (possibility to customize keys func-
tions and to set menus visibility).
In addition to standard features as water temperature
control (with possibility to choose LWT/EWT probe), the
control can also manage following functions.
The main features of this control system are:
DHW control with anti-legionella function daily and
weekly activated,
Dynamic set point (4-20 mA, 0-1V, 0-5V, 0-10V),
Double set point,
OAT compensation,
Boiler / Electrical heater integration,
Auto adaptative function to reduce the water content of
the plant,
Managing of DHW 3 ways valve (ACCESSORY),
Advanced pump management,
Remote keyboard (ACCESSORY) with possibility to con-
nect (up to 100 m distance) without any serial interface.
Electrical board
Electric equipment is built in compliance with CE stand-
ards. Easy accessible in front of the unit – through an ac-
cess panel xed with screws – the equipment is complete
with:
Door lock main isolating switch,
Compressor contactors and fuses,
Phase sequence control,
Clamps for remote summer/winter switch,
Clamps for external ow switch,
Clamps for remote double set-point,
Clamps for external interlock,
Clamps for remote general alarm,