EDM SyScroll 40 75 Air

SyScroll 40-75 Air
|
9
Refrigerant Flow Diagram - Syscroll 40-75 Air CO
COMPONENTS
1 Compressor tandem scroll type
2 Air cooled condenser
3 Filter drier
4 Sight glass
5 Thermostatic expansion valve
6 Plate heat exchanger
7 Water inlet
8 Water outlet
9 In/Out valve
10 Flexible pipes
11 By-pass valve
12 Desuperheater (optional)
2
3
4
5
6
SH
AT
A
OIL
EQUAL.
1
SL
BT
S
M
D
OUTLET
INLET
10
10 9
9
8
H
H
7
11
HYDRAULIC
CIRCUIT
G
E
F
12
SAFETY/CONTROL DEVICES
A High pressure switch (40.5 bar)
AT High pressure transducer
BT Low pressure transducer
D Air temperature sensor
E Inlet water temperature sensor
F Outlet water temperature sensor
G Safety valve (45 bar)
M Discharge temperature sensor
S 5/16” SAE Schrader valve (charging point)
SH 5/16” SAE high pressure Schrader valve
SL 5/16” SAE low pressure Schrader valve
H Thermometer
Pipe connection with Schrader valve 1/4” SAE
°
Probes
―--― Unit side
------ Optional parts