Tender Specification SyScroll 140-360 Air CO / HP Tender Specification SERIES: SyScroll 140-360 Air EVO CO / HP / RE TYPE: Air cooled water chiller, heat pump and condensing unit TECHNOLOGY: multi-scroll compressors, R410A refrigerant CAPACITY RANGE: Cool ing 144-361 [kW] Heating 145-361 [kW]
Tender Specification SyScroll 140-360 Air CO / HP 1 General description SyScroll Air EVO CO / HP / RE units have been designed and optimized to operate with R410A refrigerant and scroll compressors Thanks to multi-scroll technology and asymmetric design in refrigerant circuits, it is possible to reach very high level of full load efficiency (EER up to 3,2 and COP up to 3,3) and seasonal performances (ESEER up to 4,3), in line with Ecodesign requirements SyScroll Air EVO CO units are available in 9 sizes, w
Tender Specification SyScroll 140-360 Air CO / HP • Low Noise (L): the units are equipped with star connected fans implying lower rotation speed. Besides lower fan deck sound emission, the chillers are supplied with compressors box to reduce the noise emissions • Super Low Noise (S): the units are equipped with star connected fans, fitted with a speed controller which allows the units to operate with a very low rotation speed.
Tender Specification SyScroll 140-360 Air CO / HP • Total Heat Recover (TR version): double circuit plate type heat exchanger to recover the total heat rejected to the condensers.
Tender Specification SyScroll 140-360 Air CO / HP version • Control platform Modular architecture, compressor envelope integration, corrective actions in border line areas, easy-friendly user interface • Several options / accessories provided with standard delivery: o Phase sequence control safe electric installation o Electronic expansion valve precision in SH control o Control circuit transformer power supply without neutral o Control data logger thermodynamic parameters recording o Water diffe
Tender Specification SyScroll 140-360 Air CO / HP 4 Compressors Compressors are of hermetic scroll type and fitted with an electronic control system ensuring protection against high temperature and excessive load. All compressors have direct-on-line starting and are mounted on rubber vibration isolators in order to minimize noise and vibration transmission 5 Evaporator Indoor heat exchangers are brazed stainless steel plate type.
Tender Specification SyScroll 140-360 Air CO / HP 6 Condenser Condenser coils are made of seamless copper tubes, arranged in staggered rows, mechanically expanded into corrugated aluminum fins. In Cooling only version (CO) condenser coils are microchannel type, made of 100% aluminium (fins, tubes and headers) with the exception of copper pipe couplings. Additional surface coating is provided for the standard delivery in order to further improve resistance to corrosion.
Tender Specification SyScroll 140-360 Air CO / HP valves, filter-drier with solid core, sight glass and electronic expansion valve. Heat pump units (HP) are additionally provided with 4-way reversing valves, suction accumulators and liquid receivers. Total heat recovery units (TR) are additionally provided with 4-way reversing valves and liquid receivers.
Tender Specification SyScroll 140-360 Air CO / HP o Unit power on / off o Unit cool / heat operation o Summary alarm signal • Remote signaling, by dry contacts: o Voltage presence o Compressors in operation o General alarm • Hydro-kit management: start-up of pump, antifreeze heater of external tank, pump anti-sticking function • Heat recovery management by means of RWT sensor at the heat recovery condenser Unit controller can display all operating parameters such as: • Return water temperature • Leaving wa
Tender Specification SyScroll 140-360 Air CO / HP • • • • • • • Evaporator antifreeze Lack of water flow Compressor operation / operating hours and start-up numbers Pump operation / operating hours Compressor thermal protection Fan thermal protection Faulty sensors 10 Safety and control devices Each unit is complete with the following safety and control devices Safety • • • • • • • • Power disconnect switch with an emergency stop function Phase sequence control High pressure switches Low pressure switch
Tender Specification SyScroll 140-360 Air CO / HP • • • • • • • • • High pressure transducers Low pressure transducers Discharge gas temperature probes Return water temperature sensor Leaving water temperature sensor (with an antifreeze function) Suction temperature sensor (for EEV control) Outdoor ambient temperature sensor Coil temperature sensors (HP only) Heat recovery temperature sensor (TR only) 11 Optional hydro kits On board mounted and remote hydro-kits are available as option.
Tender Specification SyScroll 140-360 Air CO / HP • Safety valve • Automatic air vent valve • Thermal insulation for pipes and water pump(s) On board hydro kit with buffer tank are provided with following components: • Single or double pump with low available static pressure (100 [kPa]) or high available static pressure (200 [kPa]) • Buffer tank (350 [l] from 140 to 170 size, 500 [l] from 200 to 360 size) • Expansion tank (18 [l] for all models) • Check valves (in case of 2 pumps) • Safety valve • Automati
Tender Specification SyScroll 140-360 Air CO / HP 12 Factory installed options • • • • • • • • • • • • • • • • • Lonwork protocol kit for BMS Bacnet protocol kit for BMS Compressors soft-starter Fan speed control for low ambient operation in cooling mode Double set point Power factor correction capacitors Compressor overload protection Automatic circuit breaker HP & LP gauges E-coating for Microchannel and Al/Cu coils Blue fins treatment for Al/Cu coils Condenser coils with copper fins Chiller grilles Com
Tender Specification SyScroll 140-360 Air CO / HP 13 Field installed accessories • • • • • • • • • Remote ON/OFF control Remote keyboard panel Sequencer, up to max four units Master and slave control, up to max four units Anti-vibration spring Water flow switch Water pressure switch Water filter Remote hydro kits with buffer tank, 1 or 2 low or high pressure pump(s), relevant accessories and with or without antifreeze heater 14 Conformity with standards The units are in conformity with the following stan