EDM SYSCROLL 140 360 AIR EVO

|
SYSCROLL AIR EVO
20
Model 140 170 230 260 280 300 330 360
Nominal cooling capacity (1) kW 137 155 214 244 261 288 307 341
Input power (1) kW 45,1 54,6 73,2 83,8 90,7 98,5 103,5 117,0
EER/ Energy Efciency Class (1) 3,03/B 2,83/C 2,92/B 2,91/B 2,88/C 2,92/B 2,97/B 2,91/B
EER (*)/ EER (**) (1) 3,08/2,86 2,86/2,69 2,96/2,75 2,95/2,73 2,91/2,71 2,96/2,75 3,02/2,78 2,95/2,74
SEER (3) 3,8 3,95 4,13 4,05 4,1 3,83 3,8 3,93
h
sc
(3)
149 155 162 159 161 150 149 154
SEER(*) / SEER(**)(3) 3,95 4,08 4,22 4,13 4,2 3,93 3,8 4,05
h
sc
(*)/ h
sc
(**)(3)
155 160 166 162 165 154 149 159
Nominal heating capacity (2) kW 145 166 229 262 280 306 327 361
Input power (2) kW 44,9 51,6 70,9 81,7 87,4 94,9 101,9 112,6
COP/ Energy Efciency Class (2) 3,23/A 3,21/A 3,23/A 3,21/A 3,20/A 3,22/A 3,21/A 3,21/A
COP (*)/COP (**) (2) 3,28/3,05 3,25/3,05 3,27/3,03 3,26/3,01 3,25/3,02 3,27/3,02 3,26/2,99 3,26/3,02
Nominal heating capacity (6) kW 149 170 234 268 286 311 334 368
Input power (6) kW 37,2 43,6 58,7 67,8 72,3 77,8 83,7 92,7
COP (6) 4,00 3,90 3,98 3,96 3,95 4,00 3,99 3,97
SCOP /Energy efciency class /
h
sh
(7)
3,39/A+/
133
3,42/A+/
134
3,46/A+/
135
3,48/A+/
136
3,44/A+/
135
3,51/A+/
137
3,44/A+/
135
3,48/A+/
136
Number of refrigerant circuits 2 2 2 2 2 2 2 2
Total capacity steps %
25-50-75-
100
25-50-75-
100
19-38-69-
100
17-39-67-
100
16-37-68-
100
24-48-71-
100
23-50-73-
100
25-50-75-
100
Compressor
Number 4 4 4 4 4 4 4 4
Type / Oil type Scroll / Poe
Evaporator
Number 1 1 2 2 2 1 1 1
Type Plate Plate Plate Plate Plate Plate Plate Plate
Water ow Cooling m
3
/h 23,6 26,7 36,9 42,1 45,1 49,6 53,0 58,8
Water pressure drop Cooling kPa 25 31 30 30 35 26 30 37
Water ow Heating (2) m
3
/h 24,8 28,4 39,3 45,0 47,9 52,4 56,1 62,0
Water pressure drop Heating (2) kPa 27 36 34 34 39 29 33 41
Water ow Heating (6) m
3
/h 25,5 29,1 40,1 46,0 48,9 53,3 57,3 63,1
Water pressure drop Heating (6) kPa 29 37 36 36 41 30 35 42
Water volume l 11,4 11,4 21,1 23,4 23,4 32,4 32,4 32,4
Antifreeze Heater W 130 130 130+130 130+130 130+130 130 130 130
Air cooled condenser
Number of coils 2 2 5 6 6 7 8 8
Total coil face area per coil m
2
4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4
Fans
Number of fans 3 3 5 6 6 7 8 8
Nominal speed rpm 900 900 900 900 900 900 900 900
Total airow m
3
/h 68.400 68.400 112.500 135.000 135.000 157.500 180.000 180.000
Total input power kW 5,1 5,1 8,5 10,2 10,2 11,9 13,6 13,6
Total input power(*) kW 4,5 4,5 7,5 9,0 9,0 10,5 12,0 12,0
Total input power(**) kW 7,8 7,8 13,0 15,6 15,6 18,2 20,8 20,8
External static pressure Pa 0 or 120 Pa (**)
Water Connections (Evaporator)
Type Male GAS Threaded
Inlet Diameter inch 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”
Outlet Diameter inch 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”
Water Connections (Desuperheater)
Type Male GAS Threaded
Inlet Diameter / Outlet Diameter inch 1” / 1”
Weight
Shipping kg 1.294 1.337 2.049 2.312 2.427 2.564 2.748 2.925
Operating kg 1.312 1.355 2.078 2.343 2.458 2.702 2.887 3.063
Additional weight
EC-HPF versions kg 30 30 50 60 60 70 80 80
Desuperheater versions kg 8,5 8,5 17 19 19 23 23 23
Dimensions
Length mm 4.000 4.000 3.500 3.500 3.500 4.550 4.550 4.550
Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150
Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
Acoustical data
Sound power level (4) dB(A) 90 90 92 93 93 94 95 95
Sound pressure level - (10m) (5) dB(A) 58 58 60 61 61 62 63 63
(1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air
temperature, NET value refear to EN14511.
(2) Data refers to 45°C leaving warm water temperature and 7°C ambient coil air
temperature with 87% R.H., NET value refear to EN14511.
(3) Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application
chillers.
(4) Sound levels are at fully loaded conditions. Sound power level values refear to ISO
standard 3744 and Eurovent 8/1.
(5) Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
(6) Data refers to 35 °C leaving warm water temperature and 7 °C ambient coil
air temperature with 87% R.H., NET value refear to EN14511, according to DM
28_12_12.
(7) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat
pumps.
(*) High Efciency Units (EC) with inverter fans.
(**) HPF Units with high static pressure fans.
Physical Data - SYSCROLL AIR EVO HP _ - (STD-EC-HPF)
Standard, Inverter Fans and High Pressure Fan versions