TS SYSCROLL 140 360 AIR EVO GB 0617

Tender Specification
SyScroll 140-360 Air CO / HP
valves, filter-drier with solid core, sight glass and electronic expansion valve.
Heat pump units (HP) are additionally provided with 4-way reversing valves,
suction accumulators and liquid receivers.
Total heat recovery units (TR) are additionally provided with 4-way reversing
valves and liquid receivers.
9 Control panel
A new optimized control with an easy-friendly interface, manages unit
operation under different load and temperature condition and can provide:
Compressor management
o Power on/off
o Anti-cycle
o Tandem / trio unloading for high pressure, high temperature and/or
high compressor pressure ratio
Chilled and hot water temperature regulation (return water temperature
RWT - P+I type or leaving water temperature LWT - neutral band type)
Automatic control of suction superheating though electronic expansion
valve with optimized functions (cooling, heating, start-up and defrost)
Evaporator antifreeze protection
Defrost management
High and low pressure operating conditions management
External interlocks management
Remote control management