Chiller SYSCROLL 400-900 AIR EVO Air Cooled Water Chillers Cooling Only, Heat Pump and Total Heat Recovery Engineering Data Manual 399 to 897 kW 404 to 902 kW
SYSCROLL 400-900 AIR EVO | Key points High full load performances → EER up to 3,2 and COP up to 3,3 High seasonal performances → SEER up to 4,7 and SCOP up to 3,9 Low sound emission and high efficiency level in a single unit → Super Low Noise version Extended operating envelope for both cooling/heating operation → Brine cooling / High temperature / Polar heating versions Extension to 900 kW cooling/heating capacity → 750 to 900 sizes Electronic expansion device → Excellent control of superheating for the
| SYSCROLL 400-900 AIR EVO CO Specifications SY SCROLL SIZES Air EVO HP TR BC PH HT HPF EC CO = Cooling Only; HP = Heat Pump; TR = Total Heat Recovery; BC = Brine Cooling; PH=Polar Heat Pump. General description SYSCROLL AIR EVO CO / HP units have been designed and optimized to operate with R410A refrigerant and Scroll compressors.
SYSCROLL 400-900 AIR EVO | Cabinet The cabinet is made of heavy gauge galvanized steel. All galvanized steel components are individually painted by a special painting process before the assembly of the unit. This painting system performs a homogeneous protection to the corrosion. The painting is a polyester powder based type, colored in RAL 7040. The units are suitable for outdoor installation, directly on the building roof or at the ground level.
| SYSCROLL 400-900 AIR EVO Heat recovery temperature Unit controller can display various alarms and operation status: Low / High pressure Evaporator antifreeze Lack of water flow Compressor operation / operating hours and start-up numbers Pump operation / operating hours Compressor thermal protection Fan thermal protection Faulty sensors Safety and control devices Each unit is complete with the following safety and control devices Safety: Power disconnect switch with an emergency stop function Phase sequ
SYSCROLL 400-900 AIR EVO | Lonworks (RS485) interface Bacnet (RS485) interface Bacnet (Ethernet) interface ModBus (Ethernet) interface Sequencer, up to max four units Master and slave control, up to max four units Anti-vibration spring Water flow switch Water pressure switch Water filter Remote hydro kits with buffer tank, 1 or 2 low or high pressure pump(s), relevant accessories and with or without antifreeze heater Units are built in conformity with following standards: Performance EN14511 EN14825
| SYSCROLL 400-900 AIR EVO Accessories & Options (continued) SYSCROLL AIR EVO Delivery Abbreviation Description & Benefit Remote keyboard panel Accessory Modbus protocol kit for BMS (RS485) Std/Option MBS It allows the integration of the unit with BMS with Modbus protocol through RS485 port. Lonwork protocol kit for BMS (RS485) Option LON It allows the integration of the unit with BMS with Lonwork Network.
SYSCROLL 400-900 AIR EVO | Refrigerant Flow Diagram - SYSCROLL 400-900 AIR EVO CO M A S AT A S 7 S 1 G 5 S 6 2 B BT S S EEV CONTROL 5 UNIT CONTROL C S E F 4 3 8 COMPONENTS 1 Scroll type compressor 2 Air cooled condenser 3 Filter drier 4 Electronic expansion valve 5 Globe valve 6 Heat exchanger (dual type) 7 Desuperheater (optional) 8 Sight glass 5 SAFETY/CONTROL DEVICES A High pressure switch AT High pressure transducer AF Access fitting sae flare 3/8” B Low pressure switch BT Low
| SYSCROLL 400-900 AIR EVO S A A AT S M Refrigerant Flow Diagram - SYSCROLL 400-900 AIR EVO HP 12 ON 8 2 G 5 11 9 S S S B H BT UNIT CONTROL C N EEV CONTROL 6 G F D 5 E 7 6 6 5 10 4 3 6 COMPONENTS 1 Scroll type compressor 2 Air cooled condenser 3 Filter drier 4 Electronic expansion valve 5 Globe valve 6 Check valve 7 Liquid receiver 8 Four-way valve 9 Suction accumulator 10 Sight glass 11 Heat exchanger (dual type) 12 Desuperheater (option) 5 SAFETY/CONTROL DEVICES A High
SYSCROLL 400-900 AIR EVO | Refrigerant Flow Diagram - SYSCROLL 400-900 AIR EVO BC M S A A AT S 7 S 1 9 S BT 6 2 G 5 B S D 5 C F E UNIT CONTROL EEV CONTROL AF S 8 4 COMPONENTS 1 Scroll type compressor 2 Air cooled condenser 3 Filter drier 4 Electronic expansion valve 5 Globe valve 6 Heat exchange (dual type) 7 Desuperheathers (optional) 8 Sight glass 9 suction accumulator SAFETY/CONTROL DEVICES A High pressure switch AT High pressure transducer AF Access fitting sae flare 3/8” B Low
| SYSCROLL 400-900 AIR EVO Refrigerant Flow Diagram - SYSCROLL 400-900 AIR EVO TR E F M S A A AT S ON 10 9 1 S G B 6 BT S S C F S G S 4 12 5 3 8 AF COMPONENTS 1 Compressor tandem/Trio Scroll Type 2 Air cooled condenser 3 Filter drier 4 Electronic expansion valve 5 Globe valve 6 Heat exchanger 8 Sight glass 9 Four-way valve 10 Heat recover 11 Liquid receiver 12 Check valve 13 Suction D 5 5 UNIT CONTROL E 2 11 12 EEV CONTROL G 5 SAFETY/CONTROL DEVICES A High pressure
SYSCROLL 400-900 AIR EVO | Operating Limits - SYSCROLL AIR EVO CO - Cooling Mode Operating limits 400 SYSCROLL AIR EVO CO Liquid Leaving fluid temperature range Unite power supply2 1 2 600 670 Water with glycol1 °C from-10 to +5 K from 3 to 7 bar 6 -/EC °C from +10 to +48 S/EC S °C from-18 to +48 HT °C Recommended system chilled water volume Minimum capacity step 530 from +5 to +18 Temperature drop Entering air temperature range in full load operation 490 °C Maximum operating pr
| SYSCROLL 400-900 AIR EVO Operating Limits - SYSCROLL AIR EVO HP - Cooling Mode Operating limits 400 SYSCROLL AIR EVO HP Liquid Leaving fluid temperature range 580 620 670 Water with glycol °C from-3 to +5 K from 3 to 7 bar 6 -/EC °C from +10 to +46 S/EC S °C from-18 to +46 Recommended system chilled water volume Minimum capacity step Unite power supply1 1 530 from +5 to +18 Maximum operating pressure Entering air temperature range in full load operation 490 °C Temperature dr
SYSCROLL 400-900 AIR EVO | Operating Limits - SYSCROLL AIR EVO HP - Heating Mode Operating limits 400 SYSCROLL AIR EVO HP Liquid Leaving fluid temperature range Water Temperature drop Maximum operating pressure Ambient temperature Entering air temperature range in full load operation 490 530 580 620 670 °C from +25 to +55 K from 3 to 7 bar 6 - °C from-10 to +20 S/EC/EC S °C from-10 to +35 PH °C Recommended system chilled water volume Minimum capacity step Unite power supply1 1 4
| SYSCROLL 400-900 AIR EVO Correction Factors Fouling factors EVAPORATOR CONDENSER Fouling factor (m2.°C/kW) Cooling capacity factor Power input factor Fouling factor (m2.°C/kW) Cooling capacity factor Power input factor 0.044 1.000 1.000 0.044 1.000 1.000 0.088 0.987 0.995 0.088 0.987 1.023 0.176 0.964 0.985 0.176 0.955 1.068 0.352 0.915 0.962 0.352 0.910 1.135 Altitude factors Altitude (m) Cooling capacity factor Power input factor 0 1.000 1.000 600 0.987 1.
SYSCROLL 400-900 AIR EVO | Physical Data - SYSCROLL AIR EVO CO _ / EC / HPF -Standard / EC / HPF versions Main data Model Nominal cooling capacity1 Input power1 EER1 400 450 490 530 600 670 750 800 850 900 kW 398,8 446,1 487,7 533,9 597,1 667,3 748,3 797,9 847,2 896,7 kW 128,6 142,8 157,1 172,1 192,1 215,0 241,7 257,4 272,4 286,7 kW/kW 3,10 3,12 3,10 3,10 3,11 3,10 3,10 3,10 3,11 3,13 A A A A A A A A A A Eurovent energy classification 1 EER 75% kW/kW
| SYSCROLL 400-900 AIR EVO Physical Data - SYSCROLL AIR EVO CO S / EC S - Super low noise / EC Super low noise versions Main data Model Nominal cooling capacity 1 Nominal input power 1 EER 1 400 450 490 530 600 670 750 800 850 kW 396,0 440,4 480,4 524,8 585,3 651,7 743,4 792,2 838,6 kW 127,2 141,4 156,0 171,4 192,0 215,6 238,6 254,6 269,6 kW/kW 3,11 3,11 3,08 3,06 3,05 3,02 3,12 3,11 3,11 A A B B B B A A A EUROVENT energy classification 1 EER 75% kW/k
SYSCROLL 400-900 AIR EVO | Physical Data - SYSCROLL AIR EVO CO HT - High temperature version Main data Model Nominal cooling capacity 1 Nominal input power 1 EER 1 400 450 490 530 600 670 750 800 850 kW 411,2 455,8 497,3 543,1 607,2 678,7 768,3 820,5 867,0 kW 123,4 138,4 152,2 167,3 186,4 208,9 234,2 249,2 265,0 kW/kW 3,33 3,29 3,27 3,25 3,26 3,25 3,28 3,29 3,27 A A A A A A A A A EUROVENT energy classification 1 EER 75% kW/kW 3,85 3,87 3,90 3,80 3,85
| SYSCROLL 400-900 AIR EVO Physical Data - SYSCROLL AIR EVO HP _ / EC / HPF - Standard / EC / HPF versions Main data Model Nominal capacity / cooling operation 1 Nominal input power / cooling operation 1 EER 1 400 450 490 530 580 620 670 750 800 850 900 kW 373,5 419,2 454,5 489,7 535,7 581,5 625,4 701,4 748,1 795,2 838,7 kW 132,3 147,8 160,9 173,0 190,2 206,1 221,5 247,4 263,8 280,5 295,4 2,82 2,84 2,82 2,83 2,82 2,82 2,82 2,84 2,84 2,83 2,84 C C C C C
SYSCROLL 400-900 AIR EVO | Model 400 450 490 530 580 620 670 750 800 850 900 Water Connections (Evaporator) Type Inlet / Outlet diameter Victaulic inch 4" / 4" 5" / 5" inch 1"1/4 / 1"1/4 6" / 6" Water Connections (Desuperheater) Type Inlet / Outlet diameter Male GAS Threaded 2" / 2" 1"1/4 / 1"1/4 Weight Shipping kg 3.671 3.828 4.302 4.634 5.094 5.429 5.566 6.614 6.797 7.028 7.193 Operating kg 3.769 3.938 4.412 4.744 5.214 5.554 5.691 6.790 6.985 7.231 7.
| SYSCROLL 400-900 AIR EVO Physical Data - SYSCROLL AIR EVO HP S / EC S - Super low noise / EC Super low noise Main data Model Nominal capacity / cooling operation 1 Nominal input power / cooling operation 1 EER 1 400 450 490 530 580 620 670 750 800 kW 371,2 417,3 453,4 487,3 531,4 578,6 621,5 701,5 743,2 kW 128,1 143,6 156,5 167,6 183,3 199,0 214,1 241,4 256,6 kW/kW 2,90 2,91 2,90 2,91 2,90 2,91 2,90 2,91 2,90 B B B B B B B B B EUROVENT energy classific
SYSCROLL 400-900 AIR EVO | Model 400 450 490 530 580 620 670 750 800 Water Connections (Desuperheater) Type Inlet / Outlet diameter Male GAS Threaded inch 1"1/4 / 1"1/4 2" / 2" 1"1/4 / 1"1/4 Weight Shipping kg 4.033 4.183 4.654 4.991 5.447 5.794 5.934 7.321 7.495 Operating kg 4.131 4.293 4.764 5.101 5.567 5.919 6.059 7.497 7.683 Length mm 6.680 6.680 7.760 7.760 8.800 9.850 9.850 12.050 12.050 Width mm 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.
| SYSCROLL 400-900 AIR EVO Physical Data - SYSCROLL AIR EVO TR _ / EC / HPF - Standard / EC / HPF versions Main data 400 450 490 530 600 670 750 800 850 900 Nominal cooling capacity1 Model kW 396,5 434,7 475,2 519,8 583,1 654,5 736,1 793,0 833,2 873,4 Nominal input power1 kW 116,6 131,5 144,9 159,3 177,2 197,2 221,8 233,7 249,1 264,2 Nominal heat rejection1 kW 513,1 566,1 620,1 679,2 760,3 851,7 957,9 1026,6 1082,3 1137,6 kW/kW 3,40 3,31 3,28 3,26 3,29
SYSCROLL 400-900 AIR EVO | Electrical Data Compressors data: CO / TR units 400 V / 3 ph / 50 Hz Model SYSCROLL AIR EVO CO / TR 400 450 490 530 600 670 750 800 850 900 System Nominal input power Nominal input current Max input power Max running current FLA Start-up current LRA Nominal power factor 1-1 1-2 2-1 2-2 1-1 1-2 2-1 2-2 1-1 1-2 2-1 2-2 2-3 1-1 1-2 1-3 2-1 2-2 2-3 1-1 1-2 1-3 2-1 2-2 2-3 1-1 1-2 1-3 2-1 2-2 2-3 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 1-1 1-
| SYSCROLL 400-900 AIR EVO Electrical Data Compressors data: HP units 400 V / 3 ph / 50 Hz Model SYSCROLL AIR EVO HP 400 450 490 530 580 620 670 750 800 850 900 System Nominal input power Nominal input current Max input power Max running current FLA Start-up current LRA Nominal power factor 1-1 1-2 2-1 2-2 1-1 1-2 2-1 2-2 1-1 1-2 2-1 2-2 2-3 1-1 1-2 1-3 2-1 2-2 2-3 1-1 1-2 1-3 2-1 2-2 2-3 1-1 1-2 1-3 2-1 2-2 2-3 1-1 1-2 1-3 2-1 2-2 2-3 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 1-1 1-2 2-1 2-2
SYSCROLL 400-900 AIR EVO | Electrical Data Fans data: CO / TR units 400 V / 3 ph / 50 Hz Nominal input power / fan Nominal input current / fan Total input power / fan Total input current / fan SYSCROLL AIR EVO CO / TR - version Number of fans kW A kW A 400 8 1,9 3,9 15,2 31,2 450 10 1,9 3,9 19,0 39,0 490 11 1,9 3,9 20,9 42,9 530 12 1,9 3,9 22,8 46,8 600 13 1,9 3,9 24,7 50,7 670 14 1,9 3,9 26,6 54,6 750 16 1,9 3,9 30,4 62,4 800 16 1,9 3,9 30,4 62,4 8
| SYSCROLL 400-900 AIR EVO Electrical Data Fans data: CO / TR units 400 V / 3 ph / 50 Hz Nominal input power / fan Nominal input current / fan Total input power / fan Total input current / fan SYSCROLL AIR EVO CO / TR S version Number of fans kW A kW A 400 10 1,1 2,0 11,0 20,0 450 12 1,1 2,0 13,2 24,0 490 13 1,1 2,0 14,3 26,0 530 14 1,1 2,0 15,4 28,0 600 15 1,1 2,0 16,5 30,0 670 16 1,1 2,0 17,6 32,0 750 20 1,1 2,0 22,0 40,0 800 20 1,1 2,0 22,0 40
SYSCROLL 400-900 AIR EVO | Electrical Data Fans data: HP units 400 V / 3 ph / 50 Hz Nominal input power / fan Nominal input current / fan Total input power / fan Total input current / fan SYSCROLL AIR EVO HP - version Number of fans kW A kW A 400 9 1,9 3,9 17,1 35,1 450 10 1,9 3,9 19,0 39,0 490 11 1,9 3,9 20,9 42,9 530 12 1,9 3,9 22,8 46,8 580 14 1,9 3,9 26,6 54,6 620 15 1,9 3,9 28,5 58,5 670 16 1,9 3,9 30,4 62,4 750 17 1,9 3,9 32,3 66,3 800 18 1,
| SYSCROLL 400-900 AIR EVO Electrical Data Fans data: HP units 400 V / 3 ph / 50 Hz Nominal input power / fan Nominal input current / fan Total input power / fan Total input current / fan SYSCROLL AIR EVO HP S version Number of fans kW A kW A 400 11 1,9 3,9 12,1 22,0 450 12 1,9 3,9 13,2 24,0 490 13 1,9 3,9 14,3 26,0 530 14 1,9 3,9 15,4 28,0 580 16 1,9 3,9 17,6 32,0 620 17 1,9 3,9 18,7 34,0 670 18 1,9 3,9 19,8 36,0 750 21 1,9 3,9 23,1 42,0 800 2
SYSCROLL 400-900 AIR EVO | Electrical Data Pumps data: CO units 400 V / 3 ph / 50 Hz Model SYSCROLL AIR EVO CO Standard pressure (SP) Nominal input power High pressure (HP) Nominal input current Nominal input power Nominal input current kW A kW A 400 5,5 10,6 7,5 13,6 450 5,5 10,6 9,2 17,2 490 7,5 13,6 9,2 17,2 530 7,5 13,6 11,0 21,3 600 9,2 17,2 11,0 21,3 670 11,0 21,3 15,0 26,6 750* 2 x 5,5 2 x 10,6 2 x 9,2 2 x 17,2 800* 2 x 5,5 2 x 10,6 2 x 9,2 2 x 17,2
| SYSCROLL 400-900 AIR EVO Electrical Data Main unit data: CO / TR units 400 V / 3 ph / 50 Hz SYSCROLL AIR EVO CO / TR - version Nominal input current Total input current Nominal input power Total input power Start-up current Unit fuses Phase wire section A A kW kW 400 226 325 135 191 A A mm2 542 400 450 254 363 150 215 580 400 240 240 490 281 403 167 236 624 630 2x185 530 308 443 185 257 664 630 2x185 600 343 492 204 289 709 630 2x185 670 377 541
SYSCROLL 400-900 AIR EVO | Electrical Data Main unit data: CO / TR units 400 V / 3 ph / 50 Hz SYSCROLL AIR EVO CO / TR S version Nominal input current Total input current Nominal input power Total input power Start-up current Unit fuses Phase wire section A A kW kW 400 215 314 130 187 A A mm2 531 400 450 239 348 144 209 565 400 240 240 490 264 386 161 229 607 630 2x185 530 290 424 177 249 645 630 2x185 600 322 471 196 281 688 630 2x185 670 354 518 21
| SYSCROLL 400-900 AIR EVO Electrical Data Main unit data: HP units 400 V / 3 ph / 50 Hz SYSCROLL AIR EVO HP - version Nominal input current Total input current Nominal input power Total input power Start-up current Unit fuses Phase wire section A A kW kW 400 234 331 133 179 A A mm2 657 400 450 260 369 149 199 695 400 240 240 490 286 404 163 219 649 630 2x185 530 311 439 176 239 684 630 2x185 580 341 481 194 261 726 630 2x185 620 368 520 210 281
SYSCROLL 400-900 AIR EVO | Electrical Data Main unit data: HP units 400 V / 3 ph / 50 Hz SYSCROLL AIR EVO HP S version Nominal input current Total input current Nominal input power Total input power Start-up current Unit fuses Phase wire section A A kW kW 400 242 339 137 183 A A mm2 664 400 450 268 377 153 203 703 400 240 240 490 293 412 167 223 657 630 2x185 530 319 447 180 243 692 630 2x185 580 349 489 198 265 734 630 2x185 620 376 528 214 285 85
| SYSCROLL 400-900 AIR EVO Sound data: CO / TR units 63 125 250 500 1000 2000 4000 8000 Sound Power dB(A) 1 400 108 101 93 87 86 81 75 71 92 60 450 109 102 94 88 87 82 76 71 93 61 490 110 103 94 88 87 82 76 72 93 60 530 110 103 95 88 87 82 76 72 94 61 600 110 103 95 89 88 83 77 73 94 61 670 111 104 95 89 88 83 77 73 94 61 750 111 104 96 90 89 84 78 73 95 62 800 111 104 96 90 89 84 78 74 95 62 850 112 105
SYSCROLL 400-900 AIR EVO | Frequency (Hz) Model Sound Power dB(A) 1/3 Sound Pressure dB(A) 2/3 63 125 250 500 1000 2000 4000 8000 400 117 109 100 93 92 87 81 76 99 67 450 117 110 101 94 93 88 82 77 100 67 490 118 110 101 95 94 88 82 77 100 67 530 118 111 102 95 94 89 82 78 101 68 600 118 111 102 95 94 89 83 78 101 68 670 119 111 102 96 95 89 83 78 101 68 750 120 112 103 96 95 90 84 79 102 69 800 120 112 103 96 95
| SYSCROLL 400-900 AIR EVO 63 125 250 500 1000 2000 4000 8000 Sound Power dB(A) 1 400 95 90 86 84 81 76 71 65 86 53 450 96 91 87 84 82 77 71 66 87 54 490 96 91 87 84 82 77 71 66 87 54 530 96 91 88 85 82 78 72 67 87 54 580 97 92 88 85 83 78 72 67 88 55 620 97 92 88 85 83 78 73 67 88 55 670 98 92 89 86 83 79 73 68 88 55 750 98 93 89 86 84 79 73 68 89 56 800 98 93 89 87 84 79 74 68 89 56 Sound Pressu
SYSCROLL 400-900 AIR EVO | Cooling Capacities and Input power - SYSCROLL AIR EVO CO / EC / HPF - Version Outdoor air temperature °C 25 LWT CC1 °c 400 450 490 530 600 670 750 800 850 900 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 kW 402,6 429,4 448,4 467,0 485,8 504,1 533,5 451,7 481,5 503,0 524,1 545,5 566,3 599,6 496,9 529,2 553,3 577,0 601,1 624,6 661,9 543,
| SYSCROLL 400-900 AIR EVO Cooling Capacities and Input power - SYSCROLL AIR EVO CO / EC S Version Outdoor air temperature °C 25 LWT CC1 °c 400 450 490 530 600 670 750 800 850 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 kW 399,8 426,3 445,2 463,6 482,4 500,5 529,7 445,9 475,3 496,5 517,3 538,5 559,0 591,9 489,4 521,2 545,0 568,3 592,1 615,2 651,9 534,7 569,4 595,4 620,9 646,8
SYSCROLL 400-900 AIR EVO | Cooling Capacities and Input power - SYSCROLL AIR EVO CO HT Version Outdoor air temperature °C 25 LWT CC1 °c 400 450 490 530 600 670 750 800 850 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 kW 415,2 442,8 462,4 481,6 501,0 519,9 550,2 461,7 492,2 514,2 535,7 557,6 578,9 612,9 506,7 539,7 564,3 588,4 613,0 637,0 675,0 553,6 589,6 616,4 642,9 669,7 695,9 7
| SYSCROLL 400-900 AIR EVO Cooling Capacities and Input power - SYSCROLL AIR EVO HP / EC / HPF - Version Outdoor air temperature °C 25 LWT °c 400 450 490 530 580 620 670 750 800 850 CC 1 kW 5 378,2 7 403,2 9 421,2 11 438,8 13 456,8 15 474,2 18 502,1 5 423,2 7 451,3 9 471,3 11 490,8 13 510,7 15 529,9 18 560,8 5 460,4 7 490,7 9 512,6 11 534,1 13 555,9 15 577,1 18 611,1 5 497,3 7 529,9 9 553,8 11 577,3 13 601,1 15 624,3 18 661,3 5 545,6 7 581,1 9 607,6 11 633,6 13 660,1 15 685,9 18 726,8 5 59
SYSCROLL 400-900 AIR EVO | Cooling Capacities and Input power - SYSCROLL AIR EVO HP / EC / HPF - Version Outdoor air temperature °C 25 LWT °c CC1 kW 5 849,0 7 905,3 9 945,3 900 11 984,6 13 1024,4 15 1062,9 18 1124,9 GROSS data Compressor only C C = Cooling Capacity I P = Input Power 1 2 30 32 35 38 40 42 45 I P 12 CC1 I P 12 CC1 I P 12 CC1 I P 12 CC1 I P 12 CC1 I P 12 CC1 I P 12 CC1 I P 12 kW 216,1 220,6 226,5 233,0 239,2 245,7 254,4 kW 821,9 875,9 914,7 953,6 992,3 1029,5 1090,3
| SYSCROLL 400-900 AIR EVO Cooling Capacities and Input power - SYSCROLL AIR EVO HP / EC S Version Outdoor air temperature °C 25 LWT °c 400 450 490 530 580 620 670 750 800 CC 1 kW 5 379,0 7 403,4 9 422,0 11 440,3 13 458,9 15 477,0 18 505,7 5 423,6 7 451,3 9 471,7 11 491,7 13 512,0 15 531,8 18 563,3 5 460,4 7 490,6 9 512,7 11 534,4 13 556,5 15 578,0 18 612,2 5 496,3 7 528,5 9 552,6 11 576,3 13 600,4 15 623,8 18 661,1 5 542,8 7 577,8 9 604,4 11 630,6 13 657,2 15 683,2 18 724,3 5 589,2 7 627,5
SYSCROLL 400-900 AIR EVO | Heating Capacities and Input power - SYSCROLL AIR EVO HP / EC / HPF - Version Outdoor air temperature °C -7 LWT °c 400 450 490 530 580 620 670 750 800 850 900 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 HC 1 kW 267,0 269,2 270,6 / / / 301,2 302,7 304,3 / / / 325,2 327,9 329,8 / / / 349,9 352,7 354,8 / / / 388,9 38
| SYSCROLL 400-900 AIR EVO Heating Capacities and Input power - SYSCROLL AIR EVO HP / EC S Version Outdoor air temperature °C -7 LWT °c 400 450 490 530 580 620 670 750 800 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 30 35 40 45 50 55 2 0 2 7 12 15 HC1 I P 12 HC1 I P 12 HC1 I P 12 HC1 I P 12 HC1 I P 12 HC1 I P 12 HC1 I P 12 kW 270,4 271,6 271,9 / / / 304,5 305,3 305,8 / / /
SYSCROLL 400-900 AIR EVO | Cooling Capacities and Input power - SYSCROLL AIR EVO TR LWT - Recovery side °C 35 400 450 490 530 600 670 750 800 2 45 50 55 LWT °c CC1 kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 5 7 9 11 13 15 18 399,4 425,9 444,7 463,2 481,9 500,1 529,2 439,1 468,0 488,9 509,4 530,2 550,4 582,8 482,6 514,0 537,4 560,4 583,9 606,7 642,9 52
| SYSCROLL 400-900 AIR EVO LWT - Recovery side °C 35 LWT °c 5 7 9 850 11 13 15 18 5 7 9 900 11 13 15 18 CC1 2 HR1 CC1 I P 12 45 HR1 CC1 I P 12 50 HR1 CC1 I P 12 55 HR1 CC1 I P 12 HR1 kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW 839,3 895,0 934,6 973,4 1012,7 1050,9 1112,1 879,8 938,2 979,7 1020,4 1061,6 1101,6 1165,8 202,8 207,7 212,6 218,1 223,3 228,8 236,2 213,2 218,6 223,5 229,0 234,1 239,5 247,0 1042,1 1102,7 1147,2 1191,5 1236,0 1279,6 1348,3 1093,1 1156,9 1203,2 12
SYSCROLL 400-900 AIR EVO | Evaporator Water Pressure Drop Curves Water pressure drop [kPa] SYSCROLL AIR EVO CO / TR Water flow rate [l/s] Water pressure drop [kPa] SYSCROLL AIR EVO HP Water flow rate [l/s] 49
| SYSCROLL 400-900 AIR EVO Condenser Water Pressure Drop Curves Water pressure drop [kPa] SYSCROLL AIR EVO HP Water flow rate [l/s] SYSCROLL AIR EVO TR Water pressure drop [kPa] 50 Water flow rate [l/s]
SYSCROLL 400-900 AIR EVO | Variable flow hydronic systems Three options of variable water flow: Manual flow adjustment Constant delta P Constant delta T CONSTANT SPEED PUMP – VARIABLE FREQUENCY DRIVE ADJUSTMENT The unit is equipped with a hydraulic kit driven by a variable frequency drive, without providing continuous modulation of the speed. The water flow is fixed during commissioning.
| SYSCROLL 400-900 AIR EVO Available pressure head - SYSCROLL AIR EVO CO/HP Standard pressure pump (1/2PSP) SYSCROLL 400 AIR EVO CO / HP 50Hz 45Hz 40Hz 35Hz 30Hz Available Pressure Head [kPa] 250 200 150 100 50 - - 5 10 15 20 25 30 35 Water Flow Rate [l/s] SYSCROLL 450 AIR EVO CO / HP 50Hz Available Pressure Head [kPa] 250 45Hz 40Hz 35Hz 30Hz 200 150 100 50 - - 5 10 15 20 25 30 35 Water Flow Rate [l/s] SYSCROLL 490-530 AIR EVO CO / HP 50Hz 300 Available Pressure He
SYSCROLL 400-900 AIR EVO | Available pressure head - SYSCROLL AIR EVO CO/HP Standard pressure pump (1/2PSP) (continued) SYSCROLL 580 AIR EVO HP Available Pressure Head [kPa] 300 50Hz 45Hz 40Hz 35Hz 30Hz 250 200 150 100 50 - - 5 10 15 20 25 30 35 40 35 40 35 40 Water Flow Rate [l/s] SYSCROLL 600 AIR EVO CO 50Hz 45Hz 40Hz 35Hz 30Hz Available Pressure Head [kPa] 300 250 200 150 100 50 - - 5 10 15 20 25 30 Water Flow Rate [l/s] SYSCROLL 620 AIR EVO HP 50Hz Available Pressur
| SYSCROLL 400-900 AIR EVO Available pressure head - SYSCROLL AIR EVO CO/HP Standard pressure pump (1/2PSP) (continued) SYSCROLL 670 AIR EVO CO / HP 50Hz 300 Available Pressure Head [kPa] 54 45Hz 40Hz 35Hz 30Hz 250 200 150 100 50 - - 5 10 15 20 25 30 Water Flow Rate [l/s] 35 40 45 50
SYSCROLL 400-900 AIR EVO | Available pressure head - SYSCROLL AIR EVO CO/HP High pressure pump (1/2PHP) SYSCROLL 400 AIR EVO CO / HP 50Hz 45Hz 40Hz 35Hz 30Hz Available Pressure Head [kPa] 300 250 200 150 100 50 - - 5 10 15 20 25 30 35 Water Flow Rate [l/s] SYSCROLL 450 AIR EVO CO / HP 50Hz Available Pressure Head [kPa] 350 45Hz 40Hz 35Hz 30Hz 300 250 200 150 100 50 - - 5 10 15 20 25 30 35 40 Water Flow Rate [l/s] SYSCROLL 490 AIR EVO CO / HP 50Hz Available Pressure Head [kP
| SYSCROLL 400-900 AIR EVO Available pressure head - SYSCROLL AIR EVO CO/HP High pressure pump (1/2PHP) (continued) SYSCROLL 530 AIR EVO CO / HP 50Hz 45Hz 40Hz 35Hz 30Hz Available Pressure Head [kPa] 400 350 300 250 200 150 100 50 - - 5 10 15 20 25 30 35 40 35 40 35 40 Water Flow Rate [l/s] SYSCROLL 580 AIR EVO HP 50Hz 45Hz 40Hz 35Hz 30Hz Available Pressure Head [kPa] 400 350 300 250 200 150 100 50 - - 5 10 15 20 25 30 Water Flow Rate [l/s] SYSCROLL 600 AIR EVO CO 50Hz 40
SYSCROLL 400-900 AIR EVO | Available pressure head - SYSCROLL AIR EVO CO/HP High pressure pump (1/2PHP) (continued) SYSCROLL 620 AIR EVO HP 50Hz Available Pressure Head [kPa] 350 45Hz 40Hz 35Hz 30Hz 300 250 200 150 100 50 - - 5 10 15 20 25 30 35 40 45 Water Flow Rate [l/s] SYSCROLL 670 AIR EVO CO / HP 50Hz Available Pressure Head [kPa] 350 45Hz 40Hz 35Hz 30Hz 300 250 200 150 100 50 - - 10 20 30 Water Flow Rate [l/s] 40 50 60 57
| SYSCROLL 400-900 AIR EVO Available pressure head - SYSCROLL AIR EVO CO/HP Available pressure head [kPa] SYSCROLL 750-800 AIR EVO CO / HP Water flow rate [l/s] Available pressure head [kPa] SYSCROLL 850 AIR EVO CO / HP Water flow rate [l/s] SYSCROLL 900 AIR EVO CO / HP Available pressure head [kPa] 58 Water flow rate [l/s]
SYSCROLL 400-900 AIR EVO | Pump power consumption - SYSCROLL AIR EVO CO/HP Standard pressure pump (1/2PSP) SYSCROLL 400-450 AIR EVO CO / HP 50Hz 45Hz 40Hz 35Hz 30Hz Power Consump on [kW] 6 5 4 3 2 1 - - 5 10 15 20 25 35 30 Water Flow Rate [l/s] SYSCROLL 490-530 AIR EVO CO / HP 50Hz Power Consump on [kW] 8 45Hz 40Hz 35Hz 30Hz 7 6 5 4 3 2 1 - - 5 10 15 20 25 30 35 40 45 Water Flow Rate [l/s] SYSCROLL 580 AIR EVO HP 50Hz Power Consump on [kW] 12 45Hz 40Hz 35Hz 30Hz 10 8
| SYSCROLL 400-900 AIR EVO Pump power consumption - SYSCROLL AIR EVO CO/HP Standard pressure pump (1/2PSP) (continued) SYSCROLL 600 AIR EVO CO 50Hz Power Consump on [kW] 12 45Hz 40Hz 35Hz 30Hz 10 8 6 4 2 - - 10 30 20 40 50 60 Water Flow Rate [l/s] SYSCROLL 620 AIR EVO HP Power Consump on [kW] 12 50Hz 45Hz 40Hz 35Hz 20 30 40 50 30Hz 10 8 6 4 2 - - 10 60 70 Water Flow Rate [l/s] SYSCROLL 670 AIR EVO CO / HP 12 Power Consump on [kW] 60 50Hz 45Hz 40Hz 35Hz 20 30 40 50
SYSCROLL 400-900 AIR EVO | Pump power consumption - SYSCROLL AIR EVO CO/HP High pressure pump (1/2PHP) SYSCROLL 400 AIR EVO CO / HP 50Hz 45Hz 40Hz 35Hz 30Hz Power Consump on [kW] 7 6 5 4 3 2 1 - - 5 10 15 20 25 30 35 40 35 40 35 40 Water Flow Rate [l/s] SYSCROLL 450-490 AIR EVO CO / HP 50Hz Power Consump on [kW] 12 45Hz 40Hz 35Hz 30Hz 10 8 6 4 2 - - 5 10 15 20 25 30 Water Flow Rate [l/s] SYSCROLL 530 AIR EVO CO / HP 50Hz 45Hz 40Hz 35Hz 30Hz Power Consump on [kW] 12
| SYSCROLL 400-900 AIR EVO Pump power consumption - SYSCROLL AIR EVO CO/HP High pressure pump (1/2PHP) (continued) SYSCROLL 580 AIR EVO HP 50Hz 45Hz 40Hz 35Hz 30Hz Power Consump on [kW] 12 10 8 6 4 2 - - 5 10 15 20 25 30 35 40 35 40 Water Flow Rate [l/s] SYSCROLL 600 AIR EVO CO 50Hz 45Hz 40Hz 35Hz 30Hz Power Consump on [kW] 12 10 8 6 4 2 - - 5 10 15 20 25 30 Water Flow Rate [l/s] SYSCROLL 620 AIR EVO HP 50Hz 20 45Hz 40Hz 35Hz 30Hz 18 Power Consump on [kW] 62 16 14 1
SYSCROLL 400-900 AIR EVO | Pump power consumption - SYSCROLL AIR EVO CO/HP High pressure pump (1/2PHP) (continued) SYSCROLL 670 AIR EVO CO / HP 50Hz 20 45Hz 40Hz 35Hz 30Hz Power Consump on [kW] 18 16 14 12 10 8 6 4 2 - - 10 20 30 40 Water Flow Rate [l/s] 50 60 70 63
| SYSCROLL 400-900 AIR EVO Dimensions SYSCROLL 400-670 AIR EVO NOTES X Y Z Lgh A B C D G I L M Front view Side view Rear view Top view Footprint Tank outlet connection Standard hydraulic connection Total lenght Standard inlet Outlet Outlet with tank Inlet with pump/s Electrical power supply Gauge kit Main Switch Display
SYSCROLL 400-900 AIR EVO | Dimension Size Fan n Hydro connection X Y Z V W Lgh 400 CO 4230 4180 3900 240 568 4580 8 A - B- C- D 4” 400 HP 5270 4700 4430 240 568 5620 9 4” 400 CO S/HT 5270 4700 4430 240 568 5620 10 4” 400 HP S 6330 6300 4430 240 568 6680 11 4” 450 CO 5270 4700 4430 240 568 5620 10 4” 450 HP 5270 4700 4430 240 568 5620 10 4” 450 CO S/HT 6330 6300 4430 240 568 6680 12 4” 450 HP S 6330 6300 4430 240 568 6680 12 4”
| SYSCROLL 400-900 AIR EVO Lift and AVM positions - SYSCROLL 400-670 AIR EVO Side view 4 lift position Side view 8 lift position Top view 4 AVM position Top view 8 AVM position
SYSCROLL 400-900 AIR EVO | Dimension Size Fan n A B C D E Lgh 400 CO 366 3496 366 / / 4580 400 HP 366 4548 366 / / 5620 9 400 CO S/HT 366 4548 366 / / 5620 10 400 HP S 799 2537 712 1918 366 6680 11 450 CO 366 4548 366 / / 5620 10 450 HP 366 4548 366 / / 5620 10 450 CO S/HT 799 2537 712 1918 366 6680 12 450 HP S 799 2537 712 1918 366 6680 12 490 CO 799 2537 712 1918 366 6680 11 490 HP 799 2537 712 1918 366 6680 11 490 CO
| SYSCROLL 400-900 AIR EVO Dimensions SYSCROLL 750-900 AIR EVO NOTES X Y Z Lgh A B C D G I L M Front view Side view Rear view Top view Footprint Tank outlet connection Standard hydraulic connection Total lenght Standard inlet Standard outlet Outlet with tank Inlet with pump/s Electrical power supply Gauge kit Main Switch Display Dimension Size Fan n Hydro connection X Y Z Lgh 750 CO 8440 8420 7300 8900 16 A - B- C- D 6” 750 HP 9490 8420 7300 9950 17 6” 750 CO S/HT 10540 8
SYSCROLL 400-900 AIR EVO | Lift and AVM positions - SYSCROLL 750-900 AIR EVO Side view Top view Dimension Size Fan n A B C D E Lgh 750 CO 799 2537 2104 2630 366 8900 16 750 HP 366 2630 3496 2630 366 9950 17 750 CO S/HT 799 4641 712 4022 366 11000 20 750 HP S/HT 366 4022 2816 4022 366 12050 21 800 CO 799 2537 2104 2630 366 8900 16 800 HP 366 2630 3496 2630 366 9950 18 800 CO S/HT 799 4641 712 4022 366 11000 20 800 HP S/HT 366 4022 2816 4
| SYSCROLL 400-900 AIR EVO Space requirements
Notes
Systemair srl Via XXV Aprile, 29 20825 Barlassina (MB) Italy Tel. +39 0362 680 1 Fax +39 0362 680 693 info@systemair.it www.systemair.com Systemair · October 2021 · EDM SYSCROLL 400-900 AIR EVO-S-6GB(10.21) As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.