USER MANUAL DV WITH CONTROLLER VERSION 1.01.13 90925372

12—4
12.3ACfanoperationwithoutthermistorforDanfossFC101
SystemairfactorysetupisbasedonDanfossinitialization.
1422:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactorysetup:
001:Languageselection:
103:Torquecharacteristic:
 [3]AutoEnergyoptim.
120:Motorpower: Accordingtomotorplate
124:MotorCurrent: Accordingtomotorplate
125:MotorNominalSpeed: Accordingtomotorplate
129:Automaticmotoradption(AMA): [1]Kompl.motoradaptionto(Turnpoweroffandon.)
142:MotorCableLength:
Orderspecific
150:
MotorMagnetisationatzerospeed.: 0%
152:
Min.SpeedNormalMagnetisation: 10Hz
173:Flyingstart:  [1]Enable
540.0:FunctionRelay: [3]Driveready/remote
1403:Overmodulation: [1]Active
1420:ResetMode: [2]Automaticresetx2
050:LCPCopy: [1]AlltoLCP(CopyofSystemairfactorysettingstopanel)
Connections:
010V: terminal5455
Start: terminal1218
Driveready: terminal12
Jumper terminal1227