USER MANUAL DV WITH CONTROLLER VERSION 1.01.13 90925372

38
i.4.4.3.3Valvemotorandvalveforheating
Thevalveandvalvemotorarenotinstalled.2wayor3wayvalveisavailable.
i.4.4.3.4Valvemotorandvalveforcooling
TThevalveandvalvemotorarenotinstalled.2wayor3wayvalveisavailable.
i.4.5Drainingcondensatewater
Drip
traysforcollectionofcondensatewaterareinstalledunderplateheatexchangerandcoolingcoil.Each
driptrayisprovidedwithadrainageoutlet.Awatertrapisalwaysnecessary.Toavoidfreezeupsandfrost
burstsofwatertrapandpipes,sufficientinsulationisrecommendedandinstallationofheating
between
theinsulationandwatertrap/pipescouldevenbenecessary(insulation,heatingandcontrollerforthe
heatingarenotdeliveredbySystemair).
i.4.6Drainingcondensatewaterfromplateheatexchanger
Condensatefromtheplateheatexchangeriscollectedinthedriptray.Heavynegativeairpressureinthis
sectionpreventsthe
waterfromflowingoutofthedrainpipe.Awatertrapwithsufficientclosinglevelof
thewaterisessentialtoensurethatcondensatewaterflowsoutoftheunit.Theclosinglevelofthewater
trapmustbeestimatedcorrectlytoensuresafeescapeofthewater(seetheillustration
andestimatethe
minimumclosinglevelaccordingtothetable).Thepipediameterofthewatertrapandsewagesystemmust
beidenticaltothepipediameterofthedrainageoutletfromthetray.
Awatertrapisoptionalandinstallationofthewatertrapisnotincluded.
Remembertocheckthat
thereiswaterinthewatertrap.
NegativepressureP(Pa)

P H1Minimum H2
500Pa 100mm 40mm
750Pa 150mm 55mm
1.000Pa 190mm 70mm