USER MANUAL DV WITH CONTROLLER VERSION 1.01.13 90925372

43
k.6.7Firealarmfunction
k.6.7.1Externalfiresignalthatindicateblockorrun
Theunitisavailablewithoutcomponentsforthisfunction.Thecontrollerisasstandardconfiguredfor
ordinaryrunningwhenthecontactisclosed(NC).Byopencontactsthefansstopandthedampersclose.If
disconnected,fireis
indicatedandtheunitwillstopuntilthesignalisreconnected.Onthesitequalified
techniciansareabletochangetheconfiguration.
k.6.7.2Externalfiresignal
Theunitisdeliveredwithoutcomponentsforthisfunction.Thecontrolleris asstandardconfiguredfor
ordinaryrunningwhenthecontactisclosed
(NC).Byopencontactsthefansstopandthedampersclose.
Whentheunithasbeenshutdownbyafiresignal,theunithastoberestartedonthecontrolpanel.Onthe
sitequalifiedtechniciansareabletochangetheconfiguration.
k.6.7.3Twofirethermostats
Theunitisavailable
with2thermostatsinstalledintheunit1intheextractairand1inthesupplyair.The
cutofftemperatureinthethermostatsisadjustablebetween40and70˚C.Atthefactorysupplyissetat
70˚Candextractissetat40˚C.The
controllerisasstandardconfiguredtostopthefansandclosethe
dampersifathermostatisreleased.Onthesitequalifiedtechniciansareabletochangetheconfiguration.
k.6.7.4Onesmokedetectorinextractair
Thesmokedetectorhasbeeninstalledinextractairnexttothefan.Thecontroller
isasstandard
configuredtostopthefansandclosethedampersifthedetectorisreleasedbysmoke.Whentheunithas
beenshutdownbyafiresignal,theunithastoberestartedonthecontrolpanel.Onthesitequalified
techniciansareabletochangethe
configuration.
k.6.8Etool‐configurationtool
TheinstallercandownloadthePCsoftwarecalledEtoolfromwww.regincontrols.comandthissoftware
enablestheinstallertoconfigureandsupervisethefunctionofthesystemviaagraphicinterface.This
softwaredisplaysalltheparameterstobewritteninacommissioningreport(thecommissioningreportis
availableasaWordfileontheCDdeliveredwiththeunit).TheTCP/IPportintheCorrigo
E28controlleris
preparedforcommunicationwiththeEtoolsoftware.
k.6.9Electricalheaterbattery
k.6.9.1ControlofheatingcapacityconnectedtounitwithSystemaircontrolsystem
Electricalheaterinstalledwithseparatecontrollerbesidetheheater.Theseparatecontrollerisdesignedfor
capacityconversionofthe010Vcontrol
signalfromthemaincontrolsystem.Theelectricheaterisnot
suppliedfromtheairhandlingunitcabinetasthecabinetisnotdesignedtosupplytheheaterwithpower.
Nopowersupplycablesareconnectedtotheelectricheater.Theseparatecontrolleriswithoutsupply
disconnectingdevice.
