USER MANUAL DV WITH CONTROLLER VERSION 1.01.13 90925372

58
r.3.3Bagfilters
Releasethebagfiltercellsbyactivatingthehandlesandpulloutthefiltercellsoftheunitcasing.Theframe
profilesaretobecleanedandallsealscheckedfordamage.Thehandlesandlockingguiderailsarealsoto
be
checked
toensurethattheycanoperate
unobstructed.
Thenewfilterbagsmustbepushedcarefully
intotheunitinordertoensurethattheyaresealedproperly.Thevariousfiltersizesshouldbeplacedinan
ordercorrespondingtothewayinwhichtheunitisdesigned, andthefiltersmusthaveverticalbags.
r.3.4Panelfilters
The
filtercellguiderailsareto becleanedbeforefittingthenewfilters.
r.4.ChangingtheInternalBatteryinthecontroller
Note:
ThisprocedurerequiresknowledgeofproperESDprotection;i.e. anearthedwristbandmustbeused
!
Whenthealarm”InternalBattery”isactivatedandthebatteryLEDlightsupred,thebatteryforbackupof
programmemoryandrealtimeclockhasbecometooweak.Thebatteryisreplacedas
describedbelow.A
backupcapacitorsavesthememoryandkeepstheclockrunningforatleast10minutesafterthepower
supplyisremoved.Therefore,ifthebatteryreplacementtakeslessthan10minutes,therewillbenoneed
toreloadtheprogram,andtheclockwillcontinuetorun
normally.
ThereplacementbatterymustbeofthetypeCR2032.

Removethecoverbypressingdownthelocking
torquesattheedgeofthecoverusingasmall
screwdriver,andatthesametimepullingtheedges
outwards.
Gripthebatteryfirmlywithyourfingersandliftit
upwardsuntilitrisesfromitsholder.Pressthenew
batteryfirmlydownint oplace.Notethatto
preservecorrectpolarity ;thebatterycanonlybe
insertedthe“rightwayround”.