Geniox GO User manualv7.2

Table Of Contents
|
81
Install sensor for registration of rotation. The sensor must
be installed to the right seen from the inspection side of
the unit. Check that collision between sensor and
brackets at the rotor is impossible. Adjust position of
sensor if necessary.
Mount the illustrated screw on the rotor for activation of
signal from the sensor.
Note:
The distance from the screw to the sensor
must not exceed 2 mm.
1. Put a V-belt around recently assembled rotor wheel. Use a beltlock with screws to fix both ends of the belt. Grind the
ends of screws if they come to other side of the belt to have a flat surface. Spare belt lock is provided in a package
attached on inner side of the rotor.
Belt lock mounting:
Grinded belt lock screws: Spare belt lock:
2. Turn the rotor by hand to make sure it rotates freely.
Annex 8 Reversible heat pump unit (in separate cover, if heat pump was delivered)
Heat pump section is a separate section in the air handling unit, containing a complete stand-alone reversible heat
pump system (heating and cooling). If the air handling unit was delivered with this section, a separate manual about
the heat pump was enclosed in the separate cover.
211728 | v7.2