Quick configuration guide Access SW 4.0 1 04 to 4.1 1.00 157618 A004
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 How to use the configuration wizard
- 4 Save commissioning settings
- 5 Quick configuration guides
- 5.1 Editable naming
- 5.2 Alarm configuration
- 5.3 Fan control type (Pressure)
- 5.4 Temperature control type (Room)
- 5.5 Extended operation
- 5.6 Fan compensation
- 5.7 CO2 control (Fan start/stop)
- 5.8 Fire/Smoke function (Fire)
- 5.9 Free cooling
- 5.10 External cooler (DX)
- 5.11 External heater (Water)
- 5.12 Changeover
- 5.13 External stop
- 5.14 Support control
Quick configuration guides |
11
1. Select Configuration from the navigation icons
2. Select Functions
3. Select Extended operation
4. Select Yes for desired extended operation fan speeds
5.5.3 Allocation
Select I/O (in-/output) placement for the extended operation speeds in the Configuration >I/O allocation set-
tings > Digital inputs menu
Overview:
Configuration > I/O allocation settings > Digital
inputs
11 Dec 10:33
Digital inputs
Device Position
Extended operation low speed
Controller Select I/O
Extended operation normal speed
Controller
DI4
Extended operation high speed
Controller Select I/O
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input of the extended operation (e.g. DI4) as position for Extended operation low speed, Extended
operation normal speed, Extended operation high speed
5. Repeat step 4 for any remaining extended operation speeds.
5.5.4 Operation settings
Adjust extended operation time to the desired stop delay in the Time settings menu.
Overview:
Time settings
11 Dec 10:33
Extended operation stop delay 0 min
Step by step:
1.
Select Time settings from the navigation icons
2. Set the desired stop delay as Extended operation stop delay
157618 | A004