Commissioning Record

6
|
Function settings
Function
Default setting
Set value
Free cooling
No
Yes
No
Yes
Running when day outdoor temp. is
above:
22 °C °C
Stop when night outdoor temp. is above:
18 °C
°C
Stop when night outdoor temp. is below:
10 °C
°C
Stop when room temp. is below:
18 °C
°C
Free cooling start/stop hour
Start: 00:00
Stop: 07:00
Start:
Stop:
Time to block heat output after free
cooling:
60 min
min
Offset from normal speed when free
cooling:
SAF: 0
EAF: 0
SAF:
EAF:
Support control
No
Yes
No
Yes
Start heating room temperature 15 °C °C
Stop heating room temperature
21 °C
°C
Start cooling room temperature
30 °C
°C
Stop cooling room temperature
28 °C
°C
Pre-heater
No
Yes
No
Yes
Start pre-heating outdoor temperature
–15 °C
°C
Stop filter drying if outdoor temperature
<0°C
°C
Stop filter drying if outdoor temperature
>50°C
°C
Stop filter drying if outdoor humidity
<65 %
%
90925501 |