Commissioning Record

Function settings
|
7
Function
Default setting
Set value
Exchanger defrosting mode
None
Temperature monitoring
Pressure monitoring
Sectional defrosting
None
Temperature monitoring
Pressure monitoring
Section defrosting
Temperature monitoring defrosting
On
Off
On
Off
Temperature sensor
Exhaust air temperature
Defrostning sensor
Exhaust air temperature
Defrosting sensor
Temperature min limit
-3°C
°C
Stop supply air fan if outdoor temp
<–25°C
°C
Hysteresis to end defrosting
-4°C
°C
Pressure monitoring defrosting
On
Off
On
Off
Stop defrosting
On
Off
On
Off
Outdoor temp. to allow defrosting
0 °C
°C
Outdoor temp. for stop of supply air fan
–10 °C
°C
Max deviation exchanger pressure to
start defrosting
25 %
%
Pressure hysteresis to end defrosting
60 %
%
Sectional defrosting
On
Off
On
Off
Temperature sensor
Exhaust air temperature
Defrostning sensor
Exhaust air temperature
Defrosting sensor
Allow fan stop defrosting if exchanger
pressure > max limit
Yes
No
Yes
No
Max allowed deviation exchanger
pressure when defrosting
150%
%
Max deviation exchanger pressure to
start defrosting
25%
%
Pressure hysteresis to end defrosting
60%
%
Setpoint temperature min limit
–4°C
°C
Temperature hysteresis to end
defrosting
4°C
°C
Calibration extract air flow
__________
Calibration exchanger pressure
__________