Commissioning Record

28
| Alarm configuration
Alarm settings Def. settings
Set value
Alarm number 93
Alarm name
Low extract air temperature
Action: No action
Level:
-
Delay:
30 m
Limit: 10°C
Alarm number 94
Alarm name High outdoor air temperature
Action: No action
Level:
-
Delay:
30 m
Limit: 40°C
Alarm number 95
Alarm name Low outdoor air temperature
Action: No action
Level:
-
Delay:
30 m
Limit: –30°C
Alarm number 96
Alarm name Freeze protection alarm 1
Action:
Fast stop
Level:
A
Delay:
1 s
Alarm number 97
Alarm name Freeze protection alarm 2
Action:
Fast stop
Level:
A
Delay:
1 s
90925501 |