GENIOX DV CONTROL SYSTEM VERSION 04.04

Table Of Contents
Cable Plan
Path
Sheet
Geniox
Access CU 40-C
-W519, -W528
Project:
Date:
Geniox-DV Control system 04.04
26-11-2018
Rev.:
initials:
M IKE
01.00
106
Sheet:
107
Next sheet:T otal sheets:
33
-W519
Cable-type:
Remark: Humidity sensor
**
Hum idity sensor
G0 (0V) G (24V)
Out 1 (0-10V)
P
-BM3
BK Black
13 2
mm²
-T13:AI7
BN Brown
13 3
mm²
-T13:24V
GY Gray
13 2
mm²
-T13:0V
-W528
Cable-type:
Remark: HP Control
Alarm
X5:25
X5:26
-Heat pump
BK Black
10 5
mm²
-T29:DI4
Defrost
pCO C9
pCO NO9
-Heat pump
BN Brown
10 8
mm²
-T28:DI5
BU Blue
10 8
mm²
-T28:REF
0-10V
X5.11
X5.10
-Heat pump
GY Gray
17 5
mm²
-T72:AO2
Start
X5.18
X5.19
-Heat pump
OG Orange
15 4
mm²
-T62:com
Cooling
X5.17
X5.16
-Heat pump
PK Pink
16 4
mm²
-T66:DO6
RD Red
17 5
mm²
-T72:0V
TP Transparant
15 4
mm²
-T62:DO2
VT Violet
16 4
mm²
-T66:com
WH White
10 6
mm²
-T29:REF