Casing. The new casing provides the
best choice for minimal energy loss.
• Thermal bridging TB2.
Thermal insulation T2.
Deflection class D1.
Air leakage class L2.
• Negative pressure: - 400 Pa.
• Possitive pressure: + 700 Pa.
Corners. Design in ABS ensures minimal
thermal bridging.
Handles and hinges. Practical handles
and hinges make it possible to disas-
semble all panels and provide a space-
saving solution that is easy to service.
Service windows. The windows have
been designed exclusively for
Systemair and provide a large area for
easy inspection.
Panels. Elimination of thermal bridges. Separation
between inner skin and outer skin (0,8 mm) with 60 mm
insulating mineral wool. Density: 60 kg/m
3
. Pre-painted steel
sheets or Aluzinc AZ 185 ensure a corrosion protection class
C4 according to the standard EN ISO 12944-2:2000.
Frame/profiles.
High corrosion resistance
Externallly pre-painted, galvanized steel and closed profiles,
1,0/1,5 mm.
• Internally aluzinc.
Service and maintenance. All panels,
doors and openings have easy access
for cleaning and service.
Transportation. Casing design and
standard packaging allows for easy
transportation.
6 | Geniox Quick guide