The heat pump U-HP is an integrated reversible
heat pump system built into a unit section. The
system consists of a reversible heat pump and
a rotary heat exchanger that enables both heat-
ing and cooling. The unit is equipped with 2
scroll compressors, and cooling/heating capaci-
ty is stepless variable in the range 5-100%. The
heat pump is based on R-410A refrigerant. The
U-HP is equipped with a complete control
system.
The humidifier is made as a complete unit,
which includes humidification elements, tray
and frame made of stainless steel AISI 304, cir-
culation pump, irrigation regulation valves,
overflow, bleed-off regulation valve, float valve
for controlling the water supply to the tray and
valve for emptying the tray. The function of the
humidifier is based on the natural process that
water evaporates when air passes a wet sur-
face. The humidifier can either be placed in the
supply air after a heating coil or used as indirect
adiabatic cooling by placing it in the extract air
before a heat exchanger.
The dampers comply with tightness class 4 C
according to EN 1751:2014. The dampers have
counter rotating aerodynamically shaped damp-
er blades made of aluminium, which ensure a
low pressure loss when open.
The compact filter is a basic filter class G4
according to EN 779:2012 with a short building
length. It is designed on pleated filter principle.
The filter can be used as pre-filter and thereby
extend the life of the main filter.
The bag filter is a bag filter, which design pro-
vides a large filter area. The filter has a long
lifetime and thus good overall economy. The fil-
ter can be supplied in the filter classes G4, M5,
M6, F7, F8, F9 og F7 City-Flo according to EN
779:2012. F7 City-Flo is a filter with particle
and molecular filtration specially designed for
use in urban areas and areas with heavy traffic.
The sound attenuator is an absorption attenua-
tor with baffles. It is used to reduce the sound
power level from the air handling unit to the
duct system.