Quick configuration guide Access SW 4.0 1 04 to 4.1 1.00 157618 A004
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 How to use the configuration wizard
- 4 Save commissioning settings
- 5 Quick configuration guides
- 5.1 Editable naming
- 5.2 Alarm configuration
- 5.3 Fan control type (Pressure)
- 5.4 Temperature control type (Room)
- 5.5 Extended operation
- 5.6 Fan compensation
- 5.7 CO2 control (Fan start/stop)
- 5.8 Fire/Smoke function (Fire)
- 5.9 Free cooling
- 5.10 External cooler (DX)
- 5.11 External heater (Water)
- 5.12 Changeover
- 5.13 External stop
- 5.14 Support control
16
| Quick configuration guides
5.7.4 Operating settings
Adjust CO2 limits for the Fan start/stop function and adjust the minimum run time for CO2 control in the Data & Set-
tings > Demand control > CO2 menu.
Overview:
Data & Settings > Demand control > CO2
11 Dec 10:33
Start limit fan start/stop
800 ppm
Stop hysteresis fan start/stop
160 ppm
Min time for CO2 control 20 min
Step by step:
Note:
Setpoint CO2 not active for this configuration. Setpoint CO2 is only used by CO2 function Mixing damper.
1.
Select Data & Settings from the navigation icons
2. Select Demand control
3. Select CO2
4. Set Start limit fan start/stop to the desired CO2 level to start the fan start/stop function
5. Set Stop hysteresis fan start/stop to the desired amount that the CO2 level needs to decrease to end the
fan start/stop function.
5.8 Fire/Smoke function (Fire)
5.8.1 Activation
Activate the Fire function by selecting the Fire option for Fire/Smoke in the list of available functions in the Configu-
ration > Functions > Function activation menu.
Overview:
Configuration > Functions > Function activation
11 Dec 10:33
Fire/Smoke Fire
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Fire as Fire/Smoke
157618 | A004