5.10.4 Operation settings
Adjust the start/stop point for the digital output: Cooling start (SEQ-C) in the Data & Settings > Temperature
control > Cooling menu.
Overview:
Data & Settings > Temperature control > Cooling
11 Dec 10:33
Digital start output start point 10 %
Digital start output stop point 1 %
Data & Settings > Temperature control > Supply air
controller
11 Dec 10:33
Min limit supply air
14 °C
Max limit supply air
30 °C
Reduction of min limit supply air if active DX-cooling
5 °C
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Temperature control
3. Select Cooling
4. Set the desired output % to activate the digital output as Digital start output start point
5. Set the desired output % to deactivate the digital output as Digital start output stop point
6. Go back to Temperature control (use the navigation path Data & Settings > Temperature control)
7. Select Supply air controller
8. Adjust the min. allowed supply air temperature when DX-Cooling is active as Reduction of min limit supply
air if active DX-cooling.
157618 | A004