Quick configuration guides |
25
5.11 External heater (Water)
5.11.1 Activation
Select and activate an unused heating sequence (A, G or J) in the Configuration > Functions > Function acti-
vation > Heating/Cooling sequence setup menu.
Overview:
Configuration > ... > ... > Heating/Cooling sequence
setup
11 Dec 10:33
Position
Heating Cooling
Start
Heating
Start
Cooling
Name
SEQ-A
2
Off
0 % 0 %
Heating
>
SEQ-G
3
Off
0 % 0 %
Heating 2
>
SEQ-J
Off Off
0 % 0 %
External
heating/cooling
capacity
>
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Heating/Cooling sequence setup
5. 5. Assign the activation order for the heating sequence by selecting number (1-10) in column Heating for
SEQ-A, -G or -J
Note:
Off = Sequence not activated. Sequence with lower number activates before sequence with higher number.
In software version 4.0–1–05 the term “Off” is replaced with “No”.
157618 | A004