Quick configuration guide Access SW 4.0 1 04 to 4.1 1.00 157618 A004
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 How to use the configuration wizard
- 4 Save commissioning settings
- 5 Quick configuration guides
- 5.1 Editable naming
- 5.2 Alarm configuration
- 5.3 Fan control type (Pressure)
- 5.4 Temperature control type (Room)
- 5.5 Extended operation
- 5.6 Fan compensation
- 5.7 CO2 control (Fan start/stop)
- 5.8 Fire/Smoke function (Fire)
- 5.9 Free cooling
- 5.10 External cooler (DX)
- 5.11 External heater (Water)
- 5.12 Changeover
- 5.13 External stop
- 5.14 Support control
30
| Quick configuration guides
Configuration > ... > Analog outputs > Changeover 1
11 Dec 10:33
Range output
0-10 V
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input connected to the heating/cooling feedback (e.g. DI4) as position for Cooling/(Heating)
changeover 1
5. Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
6. Select Analog outputs
7. Select the analog output connected to the control signal (e.g. AO4) as position for Changeover 1
8. Select Changeover 1
9. Adjust Range output to the desired voltage range (e.g. 0-10 V).
5.13 External stop
5.13.1 Activation
Set External stop to Yes in the list of available functions in the Configuration > Functions > Function ac-
tivation menu.
Overview:
Configuration > Functions > Function activation
11 Dec 10:33
External stop
Yes
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Yes as External stop.
157618 | A004