Geniox NA Product Guide Specification

Systemair
Geniox
Series
Semi Custom AHU
Item#
23
72
13
14
acceptable VFD’s
c.
Pre-heat with [Electric, HW Coil]
d.
Bypass Dampers (If Applicable)
F.
Enthalpy/Sensible Recovery Core
1.
Sensible Core: Corrosion-resistant aluminum alloy, composed of alternating corrugated
and
flat, continuously wound layers of uniform width that guarantee laminar air flow and
low
static pressure loss.
2.
Enthalpy Core: Polymer Membrane capable of recovering sensible and latent load
through moisture transfer.
3.
Cross-flow construction type with EATR of 0.5% or lower.
4.
Free cooling capacity accomplished by bypass damper.
5.
Performance: Certified and listed by AHRI 1060.
6.
Effectiveness of Core: Documented in accordance with ASHRAE 84 and AHRI 1060.
7.
Flame Spread Index, Energy Recovery Core, UL 723: Not over 25.
8.
Smoke Developed Index, Energy Recovery Core, UL 723: Not over 50.
9.
Face and Bypass Dampers for Plate Exchanger will adhere to the following:
Factory installed dampers tested in accordance with AMCA 500.
Dampers shall have airfoil blades, extruded EPDM Seals.
Dampers shall have a maximum leakage rate of 4 CFM/square foot at 1” w.g.
(CLASS 1), and shall comply with ASHRAE 90.1.
Provide factory-mounted modulating actuators(if selected) for dampers to aide
Plate Exchanger with frost control.
Dampers shall be sized to provide economizer by allowing up to 100% of the
Outside air to bypass the Plate Exchanger.
10.
Frost Control Methodologies
a.
Timed defrost is standard on all units with Factory Controls
b.
Bypass damper frost control
c.
Pre-heat with [Electric, HW Coil]
G.
Heating and Cooling Coils
1.
All hydronic and direct expansion (DX) refrigerant coils shall meet the scheduled
performance.
2.
All coil performance shall be certified in accordance with AHRI 410, if applicable.
3.
All hydronic and direct expansion coils shall be tested at 450 psig air pressure.
4.
Coil headers shall be constructed of steel with MPT connections. Headers shall have
drain and vent connections accessible from the exterior of the unit.
5.
Hydronic coils should have minimum ½ inches OD copper tubes with minimum 0.017
inches tube wall thickness.
6.
DX coils shall be provided with seamless ½ inches OD copper tube and all joints shall
be brazed.
7.
Fins shall have a minimum thickness of 0.006 inches aluminum plate construction
8.
Provide a drain pan under each cooling coil. Drain pan shall be stainless steel
construction and double sloped towards the drain connection. Drain connection shall
be minimum 1” MPT and on the service side of the unit. Drain pan shall comply with
ASHRAE 62.1 requirements and shall allow no standing water.