G.2.5 Joining the AHU sections
Position the unit sectional modules directly opposite each other
Ensurethattheinternalfactory-ttedrubbersealingisundamaged
Section Clamps (Shipped loose) must then be installed using the table below for placement.
Side Mount Rule** Number and positioning
Service/Access Inside If height < 23-5/8” (600 mm) 1 in the middle
Ifheight≥23-5/8”(600mm) 2 pcs. 6” (150 mm) away from edge **
Ifheight≥47-1/4”(1200mm) 1 more in the middle
Back Outside If height < 23-5/8” (600 mm) 1 in the middle
If height > 23-5/8” (600 mm) 2 pcs. 6” (150 mm) away from edge
Ifheight≥47-1/4”(1200mm) 1 more in the middle
Top & Bottom Inside if unit width < 59” (1500 mm) N/A
if unit width > 59” (1500 mm) 1 in the middle
**Distances used apply to each air stream. So a Double High unit that is 55-1/8” (1400 mm) high will count as 2
streams 27-1/2” (700 mm) each.
16 | Instruction for unloading on the site as well as installation and connection
Pressthesectionstogethersothattherubberprolesareatandtheframesofthetwosectionsarejoined.Strapwithtensioneris
suitable for pressing the sections together. Note: Do not place the strap on the vertical proles because the plastic corners and the
proles are not reinforced for the heavy load and stress created by the tensioner. To avoid any load and stress on the plastic corners
and the proles the strap must be carefully placed on the bottom proles of the unit.