Instruction for unloading on the site as well as installation and connection | 19
G.2.8 Hood installation instructions
G.2.8.1 Ceiling mounted unit installation
Hoodsareshippedlooseforeldinstall.
1. Apply caulking to hood mating surface, all the way around.
2. Align hood(s) to AHU opening. Ensure appropriate clearance for doors and other access points.
3.Afxthehood(s)totheAHUusingsheetmetalscrews,beginningwithuppermosthood.
4. Clean excess caulking squeezed from between mating surfaces.
The installer is responsible for ensuring all hanging units meet
pertinent building codes.
AHUsmustbeafxedtoceilingfromthebaseframe.The
casement is not intended to support the weight of the AHU and
will fail.
G2.9 Panel cutting procedure
1. Determine the number and location of holes required for electrical conduit, piping, and control wiring as follows:
a. Check that adequate space is available inside the unit for conduit or pipe routing.
b.Donotlocateholesinpanelsthatprovideaccesstokeymaintenancecomponentssuchasltersandfanassemblies.
c.Donotlocatetheconduitorpipinginareasthatblockairoworobstructhingedaccessdoors.
2. Once a proper location is determined, drill a small pilot hole completely through the panel. Then use a hole saw or a sabre saw and
cut from each side of the panel.
Warning!
Flame and smoke can cause equipment damage, severe personal injury, or death.
Before operating unit, seal all piping and wiring holes on both inner and outer panels with an industrial grade silicone
sealantorductsealcompound.Donotuseacuttingtorchorexposepaneltore.Paneldamagecanoccur.
Note:
Support points on the unit need to be determined/
approved by factory prior to install.