Figure: Measuring Length of Coil
Spring Assembly & Adjustment
1. Through the 2 factory-drilled holes (1), insert the 2 tension spring hooks onto the bottom frame of the motor holder bracket.
2. Install 2 jam nuts onto 2 tensioning spring rods (2).
3. Attach 2 tensioning spring rods to the 2 tension springs (3).
4. Insert 2 tensioning spring rods through the swivel motor holder (4).
5. Apply LOCK TITE #242 onto the threads of the 2 tensioning spring rods above the swivel motor holder.
6. Using 2 jam nuts, fully install the 2 tensioning spring rods through to the swivel motor holder (4).
7. Adjust spring coil lengths to 1-3/4” (+/- 1/4”).
Caution
At this stage, do not install tensioning spring rods fully to allow for further adjustments.
1
2
3
4
1-3/4 1/4
Figure: Spring Adjustment Dimensions
Figure: Adjusting Spring Rods