Geniox NA Product Guide Specification

Systemair
Geniox
Series
Semi Custom AHU
Item#
23
72
13
18
AHU manufacturer prior to production release.
3. Controls by others field installed in AHU Manufacturer supplied standard Electrical Panel
b.
Controller must fit the space/volume specified. Dimensions must be approved by
AHU manufacturer prior to production release.
4. Electrical panel, disconnects, controls and all wiring field installed. No electrical by AHU
manufacturer
B. Sensors
1. The following sensors shall also be installed and pre-configured with the controller by the
manufacturer: temperature sensors (supply, return, exhaust, outdoor & entering), wheel
rotation sensor, dirty filters sensor, defrost sensor, hydronic coil frost protection sensor
and electric heating high temperature limit sensor.
2. In constant air volume applications, independent pressure sensors shall monitor both
supply and exhaust fans for constant airflow.
3. In variable air volume applications, independent pressure sensors shall monitor both
supply and exhaust fans to maintain constant duct pressure.