23Start-Up
K.2.1 Checklist, relevant values
K.3.1 Remote control
K.3.2 Speed control of fans
K.3.3 Cabinet
K.2.1.1 Checklist prior to start-up
K.3.1.1 Communication to BMS systems with MODBUS
K.3.2.1 Control system - frequency converters inside the unit
K.3.1.2 Communication to BMS systems via BACnet
K.2.1.2 Switch on power
WARNING
Do not start until all safety procedures have been completed and ensure that inspection doors are closed and locked.
Is the unit assembled correctly with its functions in the correct order?
Are the sections and ducts assembled correct?
Check that fans and anti-vibration mounts are not damaged after transportation and installation.
Are safety guards installed correctly?
Ducts - are all ducts installed?
Are the pressure transmitters installed and connected correctly? (If this is a system with pressure transmitters
in the ducts)
Main power supply:
Connected correctly? (3x400 V + N + PE)
Test of supply voltage for actuators and control signal!
Are control signals for actuators connected correctly?
Switch on power and the unit should be ready for the start-up.
The controller has been prepared for communication via RS485 communication port to a MODBUS based BMS system (Building
Management System).
The controller can work as a stand-alone system without any support from other controllers.
The controller has been prepared for BACnet TCP/IP interface. This can be used for communication with a BMS system (Building
Management System).
The controller can work as a stand-alone system without any support from other controllers.
Fanmotorrevolutionsarecontrolledbyfrequencyconverters,andtheyareconguredandtestedtocomplywiththedataforthe
unit. The frequency converter for each fan motor is installed inside the unit beside the fan motor with ca¬bles between motor and
converter. In units with complete control system the frequency converters are delivered with system parameters adapted to the
motors and the project.
The models with the cabinet on the unit are exclusively for indoor installation. Terminals are installed in the cabinet for all external
components. The number of terminals is always adapted to the individual order.
K.3 Description of functions, if control system is delivered by Systemair