GENIOX VOCLEAN IOM

36
R.4. ESP (Electrostatic Filter)
Region Interval Instructions
ESP Pan
1 Week
- 3
Months
Remove the ESP pan by sliding it toward yourself.
Clean the oil residue inside the pan at specied periods, using a cloth and mixture of water at
50-60°C and degreasing detergent.
Make sure the pan is dry before replacing it.
The Inside of the ESP
Unit
1 Week
- 3
Months
Remove the ESP collectors by sliding them toward yourself.
Oil residue can form inside the unit housing the ESP collectors. Clean the inside of the unit
thoroughly using materials such as spatula, brush, moistened cloth, degreaser etc. at specied
intervals.
If there is oil or dust residue on the electrical cable lugs on the internal surface of the door,
clean them with a moist cloth and degreaser.
Care should be taken to ensure that the inside of the unit and the electrical cable lugs are
thoroughly dry before replacing the ESP collectors.
Region Interval Instructions
ESP Collectors
3 Days
- 3
Months
Remove the ESP collectors by sliding them toward yourself.
Wash the ESP collectors at specied intervals with detergent water at 50-60°C thoroughly but
carefully without damaging the aluminum plates and ionizer wires.
Check whether any ionizer wires have been broken during the washing process. Remove the
broken wire as needed. Loop the end of the new ionizer wire in its proper place in the bus bar
as seen in “Figure 46” and pull against the spring loading force and place it on its opposite
end.
You should check for any bending in aluminum plates while cleaning the ESP collectors. If
there is bending, you can straighten the plates without damaging them, using appropriate
materials. If there are major distortions that can not be corrected, contact the manufacturer
and request a new plate.
Care should be taken to ensure that all parts which have been washed and cleaned are
thoroughly dry before replacing the ESP collectors.
If there is more than one ESP collector in your unit, make sure electrical cable lugs between
them are in proper contact.
Make sure that the ESP collectors have been installed correctly according to the direction of
air ow.
Take care that the contact gears on the door and the contact pins and the contact spring
within the collector are in the correct positions when the door is closed.
WARNING
Before performing maintenance and cleaning tasks the power supply to the ecology unit must be cut off, and the cam
switch or on/off button on the ESP section should be switched to the off position.
Wait 60 seconds for any static electricity load to be dissipated.
Top Rod of
the Ionizer
Top Rod of
the Ionizer
Tightening
the End of the
Ionizer
Collector
Section
Installation of the
Stainless Steel Ionizer End
into the Mounting Hole
Figure 36: Installation of Ionizer Wires
Recommended Maintenance Interval