Installation

EC-TMV & 5EF-TMV
Thermostatic Mixing Valve
Installation Instructions
Models EC-TMV and 5EF-TMV are a direct replacement Thermostatic
Mixing Valve (TMV) for the Mechanical Mixing Valve used on ChekPoint
(EC) and Equip (5EF) Electronic Faucets. These TMVs are tested
and certi ed to ASSE 1070. These TMVs will control and limit the
temperature of tempered water to the faucet. They are equipped
with an adjustable and lockable means to limit the maximum outlet
temperature with the intention of reducing the risk of scalding.
NOTE: This device is pre-set for approximately 100˚F (38˚C). This device must be adjusted, veri ed and locked
to a speci c maximum temperature at the time of installation.
TOOLS NEEDED
Adjustable wrench
#2 Phillips Screwdriver
Thermometer
INSTALLATION
1. Turn o Hot and Cold water supply to the faucet.
2. Disconnect the Hot and Cold  ex supply hoses at the mechanical mixing valve.
3. Loosen and unscrew the swivel nut connecting the Mechanical Mixing Valve to the  tting on the Control Module.
Remove the Mechanical Mixing Valve.
4. Install the Filter Washers supplied with the TMV in the Hot (H) and Cold (C) inlets of the TMV.
5. Install the outlet side of the TMV (OUT) into the swivel nut connection on the Control Module and tighten.
6. Connect and tighten the Hot and Cold  ex supply hoses to the corresponding Hot and Cold inlets of the TMV.
7. Turn on Hot and Cold water supply and check for leaks.
ADJUSTMENT
1. Activate the faucet several times until the outlet water temperature stabilizes. Check the temperature with the
thermometer (Caution - the outlet temperature may be excessively hot).
2. Loosen the Phillips head screw in the TMV knob approximately 6 turns and pull the knob. It should now turn.
If not, loosen the screw a little more until the knob turns.