Warranty

/A9/BAHAB&9E5AB/5E7B&B<@H9-H@"BH;<@B'AE5H-59$H7"B7H;-7,
Your “00” circulator with an Integral Flow Check (IFC) is designed for easy removal, service and replacement. Please follow these instruc-
tions to ensure proper service and operation of the circulator.
AB&9E5,
1. Disconnect power to circulator and related equipment.
2. Shut off water supply. Isolate circulator using service valves or drain system if valves are not available.
3. Allow system to cool to prevent scalding. Loosen flange bolts slowly to relieve system pressure and remove circulator from the system.
Access the IFC located in the discharge flange (Figure 8).
4. Using needle nose pliers, carefully grip the IFC body and remove slowly.
AB/5E7B&B<@,
1. Make sure the IFC pocket is clean and free of any debris.
2. Position IFC into the machined pocket inside the casing as shown in Figure 8. Firmly press
the IFC into the pocket until it snaps into place.
3. Reinstall circulator with new flange gaskets, if required.
4. Open water supply and refill system. Check for any leaks.
5. Reconnect power to circulator and check for proper operation of system.
AB/5E7;<'H&9@9A,
1. Disconnect the electrical supply.
2. Reduce system pressure to 0 psi and allow system to return to room temperature. Isolate
the circulator by closing the service valves or draining the system.
3. Remove the body bolts and swing motor assembly away from the body.
4. Transfer impeller cartridge from old motor to new motor making sure the cover plate is
between the cartridge flange and motor housing.
5. Install new motor, and reassemble circulator using the new gasket and bolts supplied.
6. Follow the “installation” procedure to start up the circulator
AB/5E7;<'H7EA@A;#'BHE44B&5!H**HAG3CD=HDFH,H***A/HC:0H**HAG3CD=HDFH,H***A/,
1. Disconnect the electrical supply.
2. Reduce system pressure to 0 psi and allow system to return to room temperature. Isolate the circulator by closing the service valves
or draining the system.
3. Remove the body bolts and swing motor assembly away from the body.
4. Pull cartridge out of the motor housing.
5. Install replacement cartridge, making sure that the cover plate is between the cartridge flange and motor.
6. Make sure the replacement cartridge corresponds to the full circulator product number. A complete parts list is available from your
local plumbing supply wholesaler.
7. Reassemble the circulator using the new gasket and bolts supplied.
8. Follow the “Installation” procedure to start up the circulator.
AB/5E7;<'H7E/E7;@9AHAG3CD=HDFH,H***A/,
1. Replacement capacitor must have same rating as originally furnished.
5;&;@B#H$EAAE<@!H4@E@B&B<@
Taco, Inc. will repair or replace without charge (at
the company’s option) any Taco 00 Series circulator
or circulator part which is proven defective under
normal use within three (3) years from the date of
manufacture.
In order to obtain service under this warranty, it is
the responsibility of the purchaser to promptly notify
the local Taco stocking distributor or Taco in writing
and promptly deliver the subject product or part, deliv-
ery prepaid, to the stocking distributor. For assis-
tance on warranty returns, the purchaser may either
contact the local Taco stocking distributor or Taco. If
the subject product or part contains no defect as
covered in this warranty, the purchaser will be billed
for parts and labor charges in effect at time of facto-
ry examination and repair.
Any Taco product or part not installed or operated in
conformity with Taco instructions or which has been
subject to misuse, misapplication, the addition of
petroleum-based fluids or certain chemical additives
to the systems, or other abuse, will not be covered
by this warranty.
If in doubt as to whether a particular substance is
suitable for use with a Taco product or part, or for
any application restrictions, consult the applicable
Taco instruction sheets or contact Taco at (401-942-
8000).
Taco reserves the right to provide replacement prod-
ucts and parts which are substantially similar in
design and functionally equivalent to the defective
product or part. Taco reserves the right to make
changes in details of design, construction, or
arrangement of materials of its products without
notification.
@E79H9--BA4H@";4H$EAAE<@!H;<H5;B%H9-HE55
9@"BAHB/AB44H$EAAE<@;B4+HE<!H$EAAE<
@!H ;&/5;B#H !H 5E$H;<75%#;<'H$EAAE<@;B4
9-H &BA7"E<@E;5;@!H 9AH -;@<B44H ;4H ;<
B--B7@H 9<5!H -9AH @"BH #%AE@;9<H 9-H @"B
B/AB44H$EAAE<@!H4B@H-9A@"H;<H@"BH-;A4@
/EAE'AE/"HE9B+
@"BHE9BH$EAAE<@;B4HEABH;<H5;B%H9-HE55
9@"BAH$EAAE<@;B4HB/AB44H9AH4@E@%@9
A!H 9AH E<!H 9@"BAH $EAAE<@!H 95;'E@;9<
9<H@"BH/EA@H9-H@E79+
@E79H $;55H<9@H BH 5;E5BH-9AH E<!H4/B7;E5
;<7;#B<@E5H ;<#;AB7@H 9AH 79<4B%B<@;E5
#E&E'B4H AB4%5@;<'H -A9&H @"BH %4BH 9-H ;@4
/A9#%7@4H 9AH E<!H ;<7;#B<@E5H 794@4H 9-
AB&9;<'H 9AH AB/5E7;<'H #B-B7@;BH /A9#
%7@4+
This warranty gives the purchaser specific rights,
and the purchaser may have other rights which vary
from state to state. Some states do not allow limita-
tions on how long an implied warranty lasts or on the
exclusion of incidental or consequential damages,
so these limitations or exclusions may not apply to
you.
FIGURE 8
View of IFC in discharge
flange of “00”
pump casing.
IFC Repair Kit #: 0012-021RP
Fits 0012 and 0013

Summary of content (1 pages)