Instructions / Assembly

ACCEPTABLE MOTOR MOUNTING POSITIONS
WARNING: Use supply wires suitable for 90°C. AVERTISSEMENT: Employer des fils d’alimentation adeqauts pour 90°C.
Always install with motor in horizontal ori-
entation. Position electrical junction box at 9
o’clock for best viewing orientation. Pump
casing may be rotated to change flow direc-
tion. Locate the arrow on the casing body to
determine flow direction.
CAUTION: To reduce the possibility of noise transmission, be sure to add vibration dampeners to piping when mounting circulator to wall
or floor joists.
ATTENTION: Pour réduire la possibilité de transmission de bruit, veillez à ajouter des amortisseurs de vibration à la tuyauterie lors du
montage du circulateur sur des chevêtres de mur ou de plancher.
WARNING: Risk of electric shock. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded, ground-
ing-type receptacle. Follow all local electrical and plumbing codes.
AVERTISSEMENT: Risque de choc électrique. Pour réduire le risque de choc électrique, veillez à ce qu'elle soit raccordée uniquement à
un réceptacle de type mise à la terre proprement mis à la terre. Respectez tous les codes de plomberie et électriques locaux.
WARNING: Disconnect power when servicing. CAUTION: Use flexible conduit only. Not for use with rigid conduit.
CAUTION: Only use union gaskets provided with fitting sets or leaks may result. Warranty will be void.
WARNING: SERVICING OF DOUBLE-INSULATED APPLIANCES. A double-insulated appliance is marked with one or more of the following:
The words “DOUBLE INSULATION” or “DOUBLE INSULATED” or the double insulation symbol (square within a square). In a double-insu-
lated appliance, two systems of insulation are provided instead of grounding. No grounding means is provided on a double-insulated appli-
ance, nor should a means for grounding be added. Servicing a double-insulated appliance requires extreme care and knowledge of the
system, and should be done by qualified service personnel. Replacement parts for a double-insulated appliance must be identical to the
parts they replace.
Figure 4: Always install with motor in
horizontal orientation.
Figure 5: Spin casing to change flow
direction.
CASING ROTATION
To rotate the pump casing, remove the 4 motor screws using a 5/32" (4 mm) allens wrench.
When rotating pump casing position, DO NOT detach motor housing from the casing. Damage to
the casing O-ring and leakage may result.Simply spin casing to the proper flow direction desired as
shown in Figure 4 and Figure 5. Reattach the 4 screws. Be sure motor is positioned correctly and
is seated evenly to prevent leakage or damage to O-ring. Tighten motor screws evenly to 25-33 in-
lbs torque.
Figure 6: Do not detach motor frame from pump
casing. Simply spin casing to the
proper flow direction.
CAUTION: Install fittings to system piping before connecting the circulator to avoid damaging the pump’s composite casing.
X