Installation Guide
Do it Once. Do it Right.
®
TACO, INC., 1160 Cranston Street, Cranston, RI 02920    Telephone: (401) 942-8000    FAX: (401) 942-2360.
TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8.    Telephone: 905/564-9422.    FAX: 905/564-9436.
Visit our web site at: http://www.taco-hvac.com
Printed in USA
Copyright 2011
TACO, Inc.
96
SR501-OR-4 Switching Relay Instruction Sheet (page 4)
TROUBLESHOOTING:
Step Five:
As in any troubleshooting procedure, it is important to isolate a prob-
lem as much as possible before proceeding. The blinking error LED
light greatly simplifies troubleshooting of the SR501-OR. If you  sus-
pect a wiring fault, return to step three and carefully check all external
wiring and wiring connections. 
Sensor Errors:
• If an outdoor sensor fault occurs, the SR501-OR will assume a
fixed  outdoor  temperature  of  32°F  (0°C)  and  will  target  the
appropriate supply water temperature. The Boiler light will blink
twice every 5 seconds to indicate the outdoor sensor error. 
• If a boiler sensor fault occurs, the SR501-OR turns the boiler off
and the  Boiler light will  blink once every  5 seconds to indicate
the boiler supply sensor error. 
Adjustment of Settings: 
• If  the  outdoor  temperature  is  cold  and  the  rooms  are  cold,
increase the Outdoor Design setting by 5°F (3°C) per day. 
• If the boiler is cycling too often, increase the Differential setting.
Testing the Sensors:
A  good  quality  test  meter  capable  of  measuring  up  to  5,000  kΩ
(1 k = 1000 Ω) is required to measure the sensor resistance. In addition
to this, the actual temperature must be measured with either a good
quality digital thermometer, or, if a thermometer is not available, a sec-
ond sensor can be placed alongside the one to be tested and the read-
ings compared. First measure the temperature using the thermometer
and then measure the resistance of the sensor at the control. The wires
from the sensor must not be connected to the control while the test is
performed. Using the chart below, estimate the temperature measured
by the sensor. The sensor and thermometer readings should be close.
If the test meter reads a very high resistance, there may be a broken
wire, a poor wiring connection or a defective sensor. If the resistance is
very low, the wiring may be shorted, there may be moisture in the sen-
sor or the sensor may be defective. To test for a defective sensor, mea-
sure the resistance directly at the sensor location.
Ω
Do not apply voltage to a sensor at any time
as damage to the sensor may result.
TECHNICAL DATA:
The installer must ensure that this control and its wiring are isolated
and/or  shielded  from  strong  sources  of  electromagnetic noise.  This
device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interfer-
ence, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
SR501-OR Boiler Reset Control Relay:
Control: Microprocessor PI control. This is not a
safety (limit) control.
Dimensions: 4
1
⁄
4
" W x 5
1
⁄
4
" H x 2
3
⁄
4
" D
Approvals: UL listed for US and Canada, Temperature
Indicating and Regulating Equipment.
Power Supply: 120/60/1 VAC, 12 amps maximum
Relays: Boiler Relay  1 amp @ 24 VAC
Circulator Relay
1
⁄
3
HP (6 FLA, 36 LRA
Sensors: NTC thermistor, 10 kΩ @ 77°F
(25°C ±0.2°C) ß=3892 
Outdoor Design Temp.: -30°F to 40°F (-35°C to 5°C) 
Boiler Minimum: 70°F or 140°F (21°C or 60°C) 
Differential: 10°F or 20°F (6°C or 12°C)
WWSD:  70°F (21°C)
TEMPERATURE RESISTANCE
°F °C
Ω
-30 -34 234,196
-20 -29 165,180
-10 -23 118,018
0 -18 85,362
10 -12 62,465
20 -7 46,218
TEMPERATURE RESISTANCE
°F °C
Ω
30 -1 34,558
40 4 26,099
50 10 19,900
60 16 15,311
70 21 11,883
80 27 9,299
TEMPERATURE RESISTANCE
°F °C
Ω
90 32 7,334
100 38 5,828
110 43 4,665
120 49 3,760
130 54 3,050
140 60 2,490
TEMPERATURE RESISTANCE
°F °C
Ω
150 66 2,045
160 71 1,689
170 77 1,403
180 82 1,172
190 88 983
200 93 829










