Product Overview

Submittal Data Information
Priority Zoning Circulators
Submittal Data # 101-054
Supersedes: 101-054 Dated: 08/15/01
Effective: 09/01/03
Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com
H
YDRONIC
C
OMPONENTS
& S
YSTEMS
Application
The Taco Priority Zoning Circulator combines the reliability of the “00” circulator with the
convenience and efficiency of a PC board mounted switching relay package. Each zoning
circulator has low and high voltage terminal strips for ease of electrical hookup, as well as
a built-in priority switch. The priority switch allows the installer to choose the zone that
requires the most attention and, when activated, run only that circulator. The priority zoning
circulator can be used in conjunction with other circulators or zone valves. It is ideal for
indirect hot water heaters, adding another zone, zoning with circulators, and for prioritizing
under-sized zones. Available in a full range of sizes from 003 - 0014.
Also look for Taco’s complete line of Switching Relays, Zone Valve Controls, and Hydro Air
Fan Controls, for all your single or multi-zone needs.
T
}
}
}
}
PC Board Layout and Electrical Hook Up
Features
“00” Reliability
• Snap-in PC Board
• Optional Integral Flow Check (IFC)
• Low and High Voltage Terminal Strips
• UL Listed
• Simplified Wiring
• LED Power Light
• 100% Factory Tested
Works With Other Circulators or Zone Valves
• Universal Thermostat Compatibility
Available In Sizes 003 - 0014
• Patented Design
• Made in the USA
Contact Ratings
Terminals 1 & 2 24VAC 1 Phase
Terminals 3 & 4 24VAC 1 Phase 5 Amps
115VAC 1 Phase 5 Amps
240VAC 1 Phase 5 Amps (max)
PR-IN & PR-OUT 115VAC 1 Phase 8 Amps
Inrush Current (max)
Live & Neutral 115VAC 1 Phase (max)
Thermostat Ratings
24VAC SPDT 2-Wire Heating
24VAC Digital Electronic
2-Wire Max Draw 30 Milliamps
Models Available
Model Application
003** Recirculation Zones
005* Residential Zones
006** Air Handlers
007* Larger Residential Zones
008* Radiant Heating Zones
009* High Head Loss-Radiant
0010* Light Commercial Zones
0011* High Flow-Radiant
0012* High Velocity
0014* High Velocity
* Cast Iron and Bronze
** Bronze Only
Cast Iron = Model # -ZF (i.e. 007-ZF5)
Bronze = Model # - ZBF (i.e. 007-ZBF5)
Integral Flow Check = Model# -ZF-IFC
(i.e. 007-ZF5-IFC)
Performance Fields
REMOVABLE PC BOARD
115 VAC POWER INPUT
115 VAC PRIORITY IN-OUT
TO T-T ON BOILER AQUASTAT
LOW VOLTAGE THERMOSTAT
OR AQUASTAT