Install Instructions
Instruction Sheet
0015-MSF-IFC Multi-Speed Cartridge Circulator
with Integral Flow Check
102-433
APPLICATION:
• Maximum operating pressure is 125 psi (862 kPa).
• Maximum water temperature not to exceed nameplate rating.
• Cast iron circulators are to be used for closed loop systems only.
• Stainless steel circulators are to be used on open, potable water systems.
• Taco  Cartridge  circulator  pumps  are  for  indoor  use  only  –  employer  uniquement  a
l´interieur.
• For use with water or maximum of 50% glycol/water mix systems only.
CAUTION:  1. The  addition  of  petroleum  based  fluids  or  certain  chemical  additives  to  systems
 utilizing TACO equipment voids the warranty.
 2.  Use  supply  wires  suitable  for  90°C  – ATTENTION:  Employer  des  fils  d´alimentation
 adequats pour 90°C.
WARNING: To avoid electrical shock, disconnect  the  power  supply  to  the  circulator  and the  main 
 electrical unit.
WARNING: Do  not  use  in  swimming  pool  or  spa  areas;  pump  has  not  been  investigated  for  this
 application.
WARNING: In  the  event  the  electrical box  has  been  pulled off  of  the housing,  DO  NOT  attempt  to
 reattach it. Use of any other screw may short out the stator windings, creating a risk of 
 electrical shock.
CAUTION: When installing electrical connections, do not apply mechanical loads to the capacitor 
 box;  otherwise,  retaining  screws  may  be  pulled  out  of  the  housing,  making  circulator 
 unusable.
S
UPERSEDES: June 1, 2014 EFFECTIVE: August 10, 2015
Plant ID# 001-4002
CAUTION: Installations at higher elevations over 5000 feet must have higher fill pressure of 20 psi
 minimum  to  prevent  pump  cavitation  and  flashing.  Premature  failure  may  result. Adjust
 expansion tank pressure to equal fill pressure. A larger size expansion tank may be required.
INSTALLATION:
1. Location – Install the 
“OO” circulator on the supply side of the boiler “pumping away” from the expansion tank as shown in
Figure 1. This is the best pump location for optimum system performance and maintaining positive system pressure. An alter-
nate location is on the boiler return line as shown in Figure 2.
2. Mounting position – Mount  circulator  with the motor in the horizontal  position. It may be mounted vertically with the
motor up, provided that the system cold fill pressure is at least 20 psi (138 kPa) to ensure proper air purging and prevent
flashing.
3. Rotating body – Body has an arrow on the front that indicates direction of flow. To rotate body, remove the four body
bolts, rotate body and replace bolts. Make sure that the junction box is NOT located underneath the circulator. (The
junction box must NOT be located in the 6 o’clock position, as viewed from the motor end.)
4. Electrical connections – Observe all applicable codes when connecting to power supply.
The  motor  is  thermally  protected,  and  does  not  require  additional  overload  protection.
Either colored wire from the capacitor box can be attached to either colored wire from the
power supply. There is no “hot” or “common” wire leading from the capacitor box. Typical
installation would be to attach the white wire to the white (common) power supply wire and
either the yellow or blue wire to the black (hot) power supply wire. The pump cannot run
backwards.
SPEED
Amps (Watts)
1 0.54 (58)
2 0.74 (79)
3 0.85 (98)
ELECTRICAL DATA
CAUTION:  Do  not  use  flat  rubber  gaskets  on  pump  flanges.  Only  use  O-ring  gaskets  provided  or
leaking will result. Warranty will be void.




