Install Instructions
0
08
0015 (High)
HIGH
MEDIUM
LOW
007 / 006
0015 (Medium)
006
0015 (Low)
Normal Mode
Green Mode
Green LED
Orange LED
6
CAUTION: Do not attempt to remove LED panel from circulator. Serious damage to circulator electronics may result.
ATTENTION: N'essayez pas de retirer le panneau de LED du circulateur. Des dommages sérieux à l'électronique du circu-
lateur peuvent en résulter.
0015e3 Performance Curves
Selection options are LOW, MEDIUM or HIGH. The 0015e3 circulator varies its speed in LOW and MEDIUM setting to maintain
a constant pressure differential (∆p-c) in the system as heating load increases or decreases. On HIGH setting, the 0015e3 runs
at full speed. If the 0015e3 detects 12 hours of constant circulation, it will automatically self-adjust to Green Mode for power opti-
mization. See chart above for operating curves and equivalent 00
®
model at each setting.
The 0015e3 has 3 Operating Settings:
• LOW - 5 feet of head constant pressure, variable speed.
• MEDIUM - 10 feet of head constant pressure, variable speed.
• HIGH - 18 feet of head max, full fixed speed.
7. Programming your 0015e3 circulator: Modify the performance of the circulator as needed by rotating the dial using a flat screw-
driver An orange LED will illuminate when the circulator is powered on. The LED will flash each time a setting is changed. See
diagram below to determine best setting for the system.The selection of the right operating curve depends on the characteristics
o
f the heating system and the actual heat demand. See cross-reference replacement chart on page 8.
Green Mode