Install Instructions
7
F
AULTS
CONTROL 
PANEL
C
AUSESREMEDIES
The circulator is 
noisy
LED on 
S
uction pressure is 
insufficient - cavitation 
Increase the system suction 
pressure within the 
permissible range.
LED on
Presence of foreign bodies 
in the impeller
Disassemble the motor and 
clean the impeller.
Loud noises of 
w
ater circulation
Flashing white 
LED
Air in the system. Pump
m
ay be air-bound. 
Vent the system. Repeat 
fill and purge steps.
Circulator is not 
running although 
the electrical 
power supply is
switched on
LED off 
Lack of power supply
Verify voltage value of the 
electric plant.
Verify the connection of the 
motor.
Circuit breaker might be
tripped
Check circuit breaker at panel
and reset if necessary
The circulator is defective Replace the pump.
Overheating
Let the pump cool down for 
some minutes. Then try to re-
start it. Verify that the water 
and ambient temperature are 
within the indicated 
temperature ranges.
LED red  The rotor is blocked
Disassemble the motor and 
clean the impeller. See 
unlocking procedure below.
Insufficient supply voltage
Verify that the power supply 
matches the data on the name 
plate.
Building does not 
get warm.
LED on
System may be air-bound
Vent system.
Repeat fill and purge steps.
8.  Troubleshooting the error codes: Listed below are potential diagnostic error codes which will appear on the LED display in case
of a malfunction.
9. Unlocking Procedure: A red LED indicates the circulator is locked or sticking. Disconnect and connect power supply to start the
automatic release process. The circulator makes 100 attempts to restart (process lasts approximately 15 minutes). Every restart
is signalled by a short white flash of LED light. If the locking is not removed through the automatic release process after 100
attempts  to  restart  the  circulator,  it  goes  into  standby  and  the  LED  remains  red.  In  this  case  follow  the  manual  procedure
described in the next steps: during any attempt, the red LED light keeps blinking; after that the circulator tries again to start. If
the locking is not removed through the automatic release process (the warning light returns to be red), perform the manual steps
described below.
1. Disconnect power supply - the warning light switches off.
2. Close both isolating valves and allow cooling. If there are no shut-off devices, drain the system so that the fluid level is
beneath that of the circulator.
3. Loosen 4 motor bolts. Remove motor from casing. Carefully pull the rotor/impeller from the motor.
4. Remove impurities and deposits from the impeller and casing.
5. Reinsert the rotor/impeller into the motor.
6. Connect power supply. Check for impeller rotation.
7. If the circulator still doesn’t run it will need to be replaced.