Install Instructions
DESCRIPTION:
The 00e
®
series 0018e
TM
circulator is a variable speed wet rotor circulator with an ECM, permanent magnet
motor. Operating modes include innitely variable xed speed, constant pressure, proportional pressure,
and activeADAPT
TM
self-adjusting proportional pressure. Adjust the operating mode with the dial or the Taco
0018e
TM
ECM Circulator Mobile App using Bluetooth
®
connectivity on your smartphone or tablet. The ECM
high-efciency motor reduces power consumption by up to 85% compared to equivalent AC permanent split
capacitor circulators.
APPLICATION:
• Maximum operating pressure: 125 psi (8.6 bar)
• Maximum water temperature: 230°F (110ºC)
• Electrical specications:
Voltage: 110-120V, 50/60 Hz, single phase
Maximum operating power: 44W
Maximum amp rating: 0.54
• Equipped with a cast iron casing and should be used for closed loop systems only
• Not suitable for open loop potable water or chilled water systems
• Taco circulator pumps are for indoor use only – employer uniquement a l’interieur
• Acceptable for use with water or maximum of 50% water/glycol solution
FEATURES:
• 3 operating modes in dial activation:
- Proportional pressure ( TRV - Panel Radiator ), variable speed - 2 variable pressure
differential settings (Med or High)
- Constant pressure ( ZV - Zone Valve ), variable speed - 2 constant pressure
differential settings (Med or High)
- Fixed speed ( ZONE CIRC - zoning with circulators ) - innitely adjustable MIN/MAX settings
• 4 operating modes in 0018e
TM
Mobile App activation:
- Fixed Speed - innitely adjustable MIN/MAX settings
- Constant Pressure - variable speed - 9 constant pressure differential settings
- Proportional Pressure - variable speed - 9 variable pressure differential settings
- activeADAPT
TM
- Designed for constant circulation systems. Automatically adjusts
to system conditions
• Multi-color LED display showing operating mode and error code diagnostics
• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation
• Nut capture feature on anges for easier t up
• Dual electrical knockouts and 6” stranded wire leads for easy wiring
• Double insulated - no ground-wire required
• Whisper quiet operation
• BIO Barrier
®
protects the pump from system contaminants
• SureStart
®
- automatic unblocking and air purging mode
• Optional 2-way ange model for easy t-up to any ange orientation
• Integral Flow Check (IFC
®
) included - Field installed
Instruction Sheet
102-557
SUPERSEDES: NEW EFFECTIVE: March 22, 2019
Plant ID No. 001-5012
0018e
TM
ECM
High-Efciency Circulator
Featuring Bluetooth
®
Communication
INSTALLATION:
WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.
AVERTISSEMENT: Ne pas utiliser dans une piscine ou un spa. La pompe n’a pas été étudiée pour ces applications.
CAUTION: The addition of petroleum based uids or certain chemical additives to systems using TACO equipment voids the warranty. Consult factory for uid
compatibility.
ATTENTION: L’ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO annule la garantie. Consultez
le fabricant pour connaître la compatibilité de liquides.
CAUTION: Installations at elevations over 5000 feet must have higher ll pressure of 20 psi minimum to prevent pump cavitation and ashing. Premature failure
may result. Adjust expansion tank pressure to equal ll pressure. A larger size expansion tank may be required.
ATTENTION: Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée de 20 psi au minimum an
d’éviter toute cavitation ou ashing de la pompe. Une défaillance prématurée peut en résulter. Réglez la pression du réservoir d’expansion de façon qu’elle soit
égale à la pression de remplissage. Un réservoir d’expansion d’une taille supérieure peut être nécessaire.
Figure 1:
Standard ange model: 0018e-F2
Part #: VR1816-HY2-FC2A01
Optional 2-way ange model: 0018e-F4
Part #: VR1816-HY2-4C2A01
1