Install Instructions

CAUTION: Do not attempt to remove LED panel from circulator. Serious damage to circulator electronics may result.
ATTENTION: N’essayez pas de retirer le panneau de LED du circulateur. Des dommages sérieux à l’électronique du circulateur peuvent
en résulter.
6
FAULTS
CONTROL
PANEL
CAUSES REMEDIES
The circulator is
noisy
LED on
Suction pressure is
insufficient - cavitation
Increase the system suction
pressure within the
permissible range.
LED on
Presence of foreign bodies
in the impeller
Disassemble the motor and
clean the impeller.
Loud noises of
water circulation
Flashing white
LED
Air in the system
Vent the system. Repeat
fill and purge steps.
LED on The flow is too high Reduce the pump speed.
Circulator is not
running although
the electrical
power supply is
switched on
LED off
Lack of power supply
Verify voltage value of the
electric plant.
Verify the connection of the
motor.
One fuse in the installation
is blown
Verify the fuses of the pump.
The circulator is defectiveReplace the pump.
Overheating
Let the pump cool down for
some minutes. Then try to re-
start it. Verify that the water
and ambient temperature are
within the indicated
temperature ranges.
LED red The rotor is blocked
Disassemble the motor and
clean the impeller. See
unblocking procedure below.
Insufficient supply voltage
Verify that the power supply
matches the data on the name
plate.
Building does not
get warm.
LED on
The circulator
performance is too low
Increase the suction head.
Increase speed or P setting.
7. Troubleshooting the error codes: Listed below are potential diagnostic error codes which will appear on the LED display in case
of a malfunction.