Submittal Sheet

LIMITED WARRANTY STATEMENT
Taco, Inc. will repair or replace without charge (at
the companys option) any Taco High Efficiency
circulator or circulator part which is proven defec-
tive under normal use within three (3) years from
the date of manufacture.
In order to obtain service under this warranty, it
is the responsibility of the purchaser to promptly
notify the local Taco stocking distributor or Taco
in writing and promptly deliver the subject product
or part, delivery prepaid, to the stocking distribu-
tor. For assistance on warranty returns, the pur-
chaser may either contact the local Taco stock-
ing distributor or Taco. If the subject product or
part contains no defect as covered in this war-
ranty, the purchaser will be billed for parts and
labor charges in effect at time of factory exami-
nation and repair.
Any Taco product or part not installed or operated
in conformity with Taco instructions or which has
been subject to misuse, misapplication, the addi-
tion of petroleum-based fluids or certain chemi-
cal additives to the systems, or other abuse, will
not be covered by this warranty.
If in doubt as to whether a particular substance
is suitable for use with a Taco product or part, or
for any application restrictions, consult the
applicable Taco instruction sheets or contact
Taco at (401-942-8000).
Taco reserves the right to provide replacement
products and parts which are substantially similar
in design and functionally equivalent to the
defective product or part. Taco reserves the right
to make changes in details of design, construc-
tion, or arrangement of materials of its products
without notification.
TACO OFFERS THIS WARRANTY IN LIEU OF
ALL OTHER EXPRESS WARRANTIES. ANY
WARRANTY IMPLIED BY LAW INCLUDING
WARRANTIES OF MERCHANTABILITY OR
FITNESS IS IN EFFECT ONLY FOR THE DURA-
TION OF THE EXPRESS WARRANTY SET
FORTH IN THE FIRST PARAGRAPH ABOVE.
THE ABOVE WARRANTIES ARE IN LIEU OF
ALL OTHER WARRANTIES, EXPRESS OR
STATUTORY, OR ANY OTHER WARRANTY
OBLIGATION ON THE PART OF TACO.
TACO WILL NOT BE LIABLE FOR ANY SPE-
CIAL, INCIDENTAL, INDIRECT OR CONSE-
QUENTIAL DAMAGES RESULTING FROM THE
USE OF ITS PRODUCTS OR ANY INCIDENTAL
COSTS OF REMOVING OR REPLACING
DEFECTIVE PRODUCTS.
This warranty gives the purchaser specific rights,
and the purchaser may have other rights which
vary from state to state. Some states do not
allow limitations on how long an implied warranty
lasts or on the exclusion of incidental or conse-
quential damages, so these limitations or exclu-
sions may not apply to you.
2019
Min
Max
Q(gpm)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
H (ft)
0
2
4
6
8
10
12
14
16
18
20
Q (l/s)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
H (m)
0
1
2
3
4
5
6
Q (m
3
/h)
43210
0015 – High
007
0015 – Low
003
Flow
Head in Feet
Med
High
Q(gpm)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
H (ft)
0
2
4
6
8
10
12
14
16
18
20
Q (l/s)
0.0 0.2 0.4 0.6 0.8 1 .0 1.2
H (m)
0
1
2
3
4
5
6
Q (m
3
/h)
43210
008
0015—Med
007
0015—Low
Flow
Head in Feet
Med
High
Q(gpm)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
H (ft)
0
2
4
6
8
10
12
14
16
18
20
Q (l/s)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
H (m)
0
1
2
3
4
5
6
Q (m
3
/h)
43210
Flow
Head in Feet
Fixed speed mode (Zone Circ) allows the installer
to ne tune the circulator ow rate to precisely
match design load conditions. It is innitely
variable between MIN/MAX settings.
Ideal for zoning with circulators.
In constant pressure mode (ZV), the circulator
maintains a constant pressure dierential (p-c) in
the system as heating load increases or decreases.
Selections options are Medium or High.
Best option for zoning with zone valves.
In proportional pressure mode (TRV), the circulator
maintains a proportional pressure dierential (p-v)
in the system as heating load increases or decreases.
Flow will change in relationship to the change in
pressure dierential. Selections options are
Medium or High.
Best option for panel radiators with thermostatic
radiator valves (TRV).
Fixed Speed Mode (MIN/MAX)Constant Pressure Mode (ZV) Proportional Pressure Mode (TRV)
The 0018e is factory-programmed for MAX Speed Setting. Simply turn the dial to change speed, operating mode or activate Mobile App.
Blue LED
min -
max
Orange LED
C
Green LED
P
Replacement Chart (6-3/8” flange to flange dimension)
Taco Grundfos Armstrong Xylem/B&G Wilo
005
006
007
008
00R
00R
3-Speed
0015
3-Speed
UP 15-10 F
UP 15-10 FR
UP 15-42 F
UP 15-42 FR
UPS 15-42 F
UPS 1558 FC
UPS 15-58 FRC
ALPHA 15-55F
ALPHA 15-55FR
Astro 230CI
Astro 230CI-R
Astro 250CI
Astro 250CI-R
Astro 20
Astro 25
Astro 30
Astro 30-3
Astro 50-3
Compass 20-20
ecocirc 19-14 auto
ecocirc 19-14 vario
NRF-22
NRF-25
NRF-9F/LW
Star S 16F
Star S 16FX
Star S 21RFC
Star S 21FX
Star S 21F
Stratos ECO
16 RFC
TTT
Constant Pressure Mode
Across a series loop system
using zone valves
Fixed Speed Mode (Min/Max)
For zoning with circulators
Proportional Pressure Mode
Across multiple panel radiators
with thermostatic radiator valves
T= thermostatic radiator valve (TRV)
Typical Applications
Fixed Speed Mode (Min/Max) For zoning with circulators
Constant Pressure Mode (ZV)
Across a series loop system using zone valves
Proportional Pressure Mode (TRV) Across multiple
panel radiators with thermostatic radiator valves
T= thermostatic radiator valve (TRV)
TTT
Constant Pressure Mode
Across a series loop system
using zone valves
Fixed Speed Mode (Min/Max)
For zoning with circulators
Proportional Pressure Mode
Across multiple panel radiators
with thermostatic radiator valves
T= thermostatic radiator valve (TRV)
TTT
Constant Pressure Mode
Across a series loop system
using zone valves
Fixed Speed Mode (Min/Max)
For zoning with circulators
Proportional Pressure Mode
Across multiple panel radiators
with thermostatic radiator valves
T= thermostatic radiator valve (TRV)