Install Instructions

DESCRIPTION:
The 0026e™ is a high-performance, variable speed, high-eciency, wet-rotor circulator
with an ECM permanent magnet motor. With 5 easy settings, its variable speed
performance curves are equivalent to the Taco 0010, 0011, 0012, 0012 3-Speed,
0013, 0013 3-Speed & 0014. Ideal for large residential and light commercial hydronic
heating, chilled water cooling and domestic hot water systems. The 0026e reduces
power consumption by up to 85% compared to equivalent AC permanent split
capacitor circulators. With a maximum of 26 feet of head and 44 gpm. It is available
in either Cast Iron or NSF certied Stainless Steel.
APPLICATION:
Maximum operating pressure: 150 psi (10.3 bar)
Maximum uid temperature: 230°F (110˚C)
Minimum uid temperature: 14°F (-10˚C)
Electrical specications:
Voltage: 115/208/230V, 50/60 Hz, single phase
Maximum operating power: 120W
Maximum amp rating: 1.05 A
Equipped with a Cast Iron or Stainless Steel casing
SS Model suitable for open loop potable water systems
Taco circulators are for indoor use only – employer uniquement a l’interieur
Acceptable for use with water or maximum of 50% water/glycol solution
FEATURES:
5 easy dial settings to match system requirements - activeADAPT, LOW, MEDIUM, HIGH or 0-10V DC input
Replaces all single speed and 3-speed circulators in its class
ECM performance equivalent to Taco’s 0010, 0011, 0012 & 0014 circulators
Multi-color LED: power on, mode setting and error code diagnostics
Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation
Nut-capture feature on anges for easier t up
Dual electrical knockouts and removable quick-connect terminal strip for easy wiring
Whisper quiet operation
BIO Barrier® protects the pump from system contaminants
SureStart® automatic unblocking and air purging mode
Rotatable control cover to allow any pump body orientation
INSTALLATION:
WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.
AVERTISSEMENT : Ne pas utiliser dans une piscine ou un spa. La pompe n’a pas été étudiée pour ces applications.
CAUTION: The addition of petroleum based uids or certain chemical additives to systems using TACO equipment
voids the warranty. Consult factory for uid compatibility.
ATTENTION : Lajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un
équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.
CAUTION: Installations at elevations over 5000 feet must have higher ll pressure of 20 psi minimum to prevent
pump cavitation and ashing. Premature failure may result. Adjust expansion tank pressure to equal ll pressure.
A larger size expansion tank may be required.
ATTENTION : Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage
plus élevée de 20 psi
au minimum an d’éviter toute cavitation ou ashing de la pompe. Une défaillance prématurée peut en résulter. Réglez la pression
du réservoir d’expansion de façon qu’elle soit égale à la pression de remplissage. Un réservoir d’expansion d’une taille supérieure
peut être nécessaire.
Instruction Sheet
102-566
SUPERSEDES: February 1, 2021 EFFECTIVE: August 16, 2021
Plant ID No. 001-5032
-1-
Figure 1
Standard ange model: 0026e-F2
Certified to
NSF/ANSI 61 & 372

Summary of content (12 pages)