007e Technical Brochure
Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.TacoComfort.com
Specifications
• Max. Shut-off Head: 10 feet
• Max. Flow: 16 gpm
• Max. Operating Pressure: 125 psi
(8.6 bar)
• Max. Water Temp: 230°F (110°C)
• Min. Water Temp: 36°F (2°C)
• Electrical specifications:
Voltage: 120V, 60 Hz
Single phase
Max. Operating Power: 44W
Max. AMP Rating: 0.54
• Equipped with a cast iron casing
and should be used for closed
loop systems only
• Not suitable for chilled water or open
loop potable water systems
• Taco circulator pumps are
for indoor use only
• Acceptable for use with water or
maximum of 50% water/glycol solution
Pump Dimensions & Weights
Electrical Data
Model Volts Hz Ph Max.Amps Max. Watts RPM
Both Models
120 60 1 .54 44 1590-4830
Motor Type ECM, Permanent Magnet, Thermally Protected
Materials of Construction:
Casing: ...............................Cast Iron
Stator Housing: .............Composite
Cartridge: .......................... Composite
Impeller: ............................Composite
Shaft: ....................................Ceramic
Bearings: ............................Carbon
Thrust Bearing: ..............Ceramic
O-Ring & Gaskets: ........EPDM
Applications
The 007e is a variable speed, high-eciency wet rotor circulator with
an ECM permanent magnet motor. Its ECM performance is equivalent
to the legendary 007 circulator and is ideal for hydronic systems zoned
with circulators or zone valves. The 007e is not suitable for chilled water
or open loop potable water systems.
Mounting Positions
Flange Type
Universal 2-Way (U)
Model
(Part Number)
Flange
Type
A B C D F G Ship Wt.
in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
007e-2F2
(VB1016-HY2-FC2A00)
S 6 152 4-1/8 104 3-3/16 80 3-1/4 82 5 126 6-3/8 161 5.8 2.6
007e-2F4
(VB1016-HY2-4C2A00)
U 6 152 4-1/8 104 3-3/16 80 3-1/4 82 5-1/8 130 6-3/8 161 6 2.7
D
G
F
C
B
A
Standard (S)
Universal 2-Way (U)
Standard (S)
Submittal Data # 101-200 Eective: 03/22/18
Supersedes: 04/20/17
Submittal Data Information
Taco 007e
®
ECM Circulator