Install Instructions
The Variable Speed - Outdoor Reset ”00” Cartridge Circulator (00-VR) is a microprocessor-based pump designed to regulate the supply
water temperature to a heating system through variable speed injection mixing. The 00-VR modulates its speed to provide outdoor reset
to the heating system. A boiler sensor installed on the return line to the boiler is used to protect the boiler against flue gas condensa-
tion.
Outdoor Reset
In order to properly control a hot water heating system, the heat supplied to the build-
ing must equal the heat lost by the building.
• The heat supplied to the building is directly proportional to the temperature of the
water and the surface area of the heating element. The higher the temperature of the
water flowing through the heating terminal, the higher the heat output.
• The heat lost from a building is dependent on the outdoor temperature. As the out-
door temperature drops, the building heat loss increases.
These two facts lead to the concept of outdoor reset which increases the supply
water temperature as the outdoor temperature drops. Using this approach, the heat
lost from the building is matched by the heat provided by the terminal units, therefore
providing more comfort and energy savings.
Reset Ratio
The Reset Ratio sets the relationship between outdoor temperature and supply
water temperature. It determines the amount the supply water temperature is raised
for every 1 degree outdoor temperature drop. For example, if a Reset Ratio of 1.2
is selected, the supply water temperature is increased by 1.2 degrees of every 1
degree of outdoor temperature drop.
Variable Speed Injection Mixing
Variable Speed Injection Mixing uses a pump as a mixing device instead of a 2-way, 3-way or 4-way valve. The 00-VR operates a pump
in order to inject hot water from the boiler loop into the cooler system loop. The speed of the pump is modulated in order to inject dif-
ferent rates of hot water into the cooler system return water. This allows for virtually any water temperature to be supplied to the heat-
ing system. Most boilers cannot operate at low temperatures, therefore the 00-VR injection pump can be modulated back in order to
prevent the boiler from operating at cold temperatures.
102-141
Instruction Sheet
Variable Speed - Outdoor Reset (00-VR)
“00” Cartridge Circulator
SUPERSEDES: May 1, 2010
EFFECTIVE: October 1, 2010