TROUBLESHOOTING:
This troubleshooting table is intended as a helpful guide and is not all inclusive. There could be other causes and solu-
tions for a non-functioning product.
FAULT / SYMPTOM CAUSE POSSIBLE SOLUTION
1. The desired mixed water temperature
cannot be obtained or valve is diffi-
cult to set.
Inlet temperatures are not within spec-
ification limits.
Hot and cold supplies are reversed.
Strainers are blocked.
Ensure inlet temperatures are within
the specified limits for the valve.
Refit the valve with Hot/Cold supplies
fitted to the correct connections.
Clean strainers.
2. Mix temperature unstable or chang-
ing over time.
Strainers are blocked.
Fluctuating supply pressures.
• Clean strainers.
Install pressure regulating valves on
both hot and cold supplies.
3. Either full hot or full cold water flow-
ing from outlet fixture.
Valve is incorrectly set.
Hot and cold supplies are reversed.
Hot/Cold water has migrated to other
inlet.
Refer also to point 1.
Adjust mix temperature as required.
Refit the valve with Hot/Cold supplies
fitted to the correct connections.
Verify the check valve is not fouled.
Clean if necessary.
4. No flow from the valve outlet.
Hot or cold water supply failure.
Strainers are blocked.
Restore inlet supplies and check mix
temperature.
Clean strainers.
5. Flow rate reduced or fluctuating.
Strainers are blocked.
Fluctuating supply pressures.
Clean strainers.
Install pressure regulating valves.
6. Mixed water temperature does not
change when temperature adjuster is
altered.
Hot and cold supplies are reversed. Refit the valve with Hot/Cold supplies
fitted to the correct connections.
7. Hot water flows into the cold water
system or vice versa.
Check valves fouled. Clean check valves, ensuring debris is
removed.
8. Valve is noisy.
Excessive water velocity.
Valve sized incorrectly.
Reduce water velocity (best achieved
by fitting a pressure regulating valve).
Check valve specifications and ensure
the appropriate valve is used for
required flow.
FLOW CURVE:
HOT
C
OLD
COLD
M
IX
COLD WATER LOOP
F
LOW REGULATOR
12" RECOMMENDED
HOT
WATER HEATER
TYPICAL ASSE 1017 INSTALLATION: