Press the button until the time-based flow rate menu is
d
isplayed as t2 (Figure 15).
Press the button again and use the or buttons
to set how many minutes the FloodBreaker waits before
shutting off the water supply when the flow exceeds 15.5
GPM (Figure 16).
Save the change by pressing the button again.
This feature allows the FloodBreaker to double check for a
leak when a volume-based leak is detected. The factory
setting is deactivated or off (E-).
When the recheck feature is activated (E1) and the
FloodBreaker detects a leak, it shuts off the water. It will re-
open after 30 seconds to see if water is actually being
drawn off. If water flow is detected the valve will close and
not open again until it is reset. If no water flow is detected
the valve will remain open and allow water usage up to the
set points.
Press the up or down button to activate (E1) or de-
activate (E-) (Figure 17).
Press the button to save the change.
This is a dry contact with a 24Volt/2amp maximum switch-
ing capability.
The primary use for this contact would be an external alarm
display or signal. The factory setting is o1.
Press the button until the current setting is shown. Use
the or button to set the contact to the required func-
tion (Figure 18). Save any changes by pressing the but-
ton again.
10
Figure 15
Figure 16
6.5 Volume-based leak secondary
check
Figure 17
6.6 Output contact
Figure 18
Setting Meaning Symbol
Contact is
deactivated
Closing contact
Opening contact
Momentary
Note: The external power supply must be used for the out-
put contact to function. It will not function on battery
power alone.